Monessen Hearth CFX24 User Manual

Page of 36
19
CFX Vent Free Fireplace System
20301726
ELECTRICAL WIRING (MILLI-VOLT)
CONNECT REMOTE RECEIVER
THESE INSTRUCTIONS SUPERSEDE THE SECTION ENTITLED “HEARTH MOUNT” IN THE 
MILLI-VOLT HAND-HELD REMOTE INSTRUCTIONS SUPPLIED WITH THE REMOTE.
1.  Remove bottom louver door.  
2.  Connect the remote connectors located in the unit.  
3.  Apply Velcro
®
 pads with self-adhesive backing to bottom of remote receiver and to floor of compart-
ment behind access panel.
4.  Attach remote receiver to firebox with Velcro
®
 pads. Control switch must face forward.
CHECK SYSTEM OPERATION
The millivolt system and individual components may be checked with a millivolt meter having a 0-1000 
mV range. Conduct each check shown in chart below by connection meter test leads to terminals as 
indicated.
A. COMPLETE MILLIVOLT SYSTEM CHECK 
  (“A” Reading - Thermostat contacts CLOSED - Control Knob “ON” - Main burner should be 
come ON)
a.  If the reading is more than 100 millivolts and the automatic valve still does not come on, replace 
the control.
b.  If the closed circuit reading (“A” reading) is less than 100 milli-volts, determine cause for low read-
ing, proceed to Section B below. 
B. Thermopile Output Reading Check  
(“B” Reading - Thermostat contacts OPEN - Main burner OFF)
1.  Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, 
then check pilot voltage, 325 millivolts minimum. If the minimum milli-volt reading is not obtainable, 
replace pilot.
 
 
 
Connect Meter 
Switch or 
Meter 
 
  Check 
To 
Leads to 
Thermostat 
Reading 
 
 
Test 
Test 
Terminals 
Contacts 
Should Be
 
Complete 
2 & 3 
Closed 
Closed 
 
 
 
System
 
Thermopile 
1 & 2 
Open 
Open 
 
 
 
Output
SKYT
ECH
OFF
ON
REM
OTE
FIRE
PLA
CE
REM
OTE
FP2113
install remote
Remote Receiver
Velcro Pad
Velcro
®
 Pad
Figure 17 - 
Install Remote Receiver 
FP2113
NOTICE
Do not place 
remote in 
combustion 
chamber.