Monessen Hearth HDV500NV/PV User Manual

Page of 64
HDV Series Direct Vent Gas Fireplace
18
56D3048
VeNtING INStAllAtIoN     
HOT
FP1955
horizontal vent cap
Figure 17 - 
Install Horizontal Vent Cap 
Vent Cap
Wood Screw
Apply Mastic to 
All Sides 
FP1955
W
ARNING
Do  not  recess  vent  termination  into  any 
wall. this will cause a fire hazard.
HOT
FP1956
vinyl siding standoff
Figure 18 - 
Installing Vinyl Siding Standoff and Termination 
Apply Mastic to All Sides 
Cut Vinyl Siding Away to Fit Standoff  
or Termination 
Wood Screw
Termination 
Bolt
Nut
Standoff #150 or 5DT-VS
(Not Required for MHSC 
Termination)
FP1956
N
ot
IC
e
For more information, refer to the instructions 
supplied with the termination.
6.  Slide the wall thimble over the vent pipe before con-
necting the horizontal run to the vent cap. Figure 19
7.  Carefully  move  the  fireplace  with  vent  assembly 
attached toward the wall and insert the vent pipe into 
the  horizontal  termination.  The  pipe  overlap  should 
be a minimum of 1Z\v". Apply silicone to the outer pipe 
connection.  Fasten  all  vent  connections  with  screws 
provided.
8.  Slide the wall thimble against the interior wall surface 
and attach with screws. Figure 19
FP1957
install firestop
Figure 19 - 
Connect Vent Cap with Horizontal Vent Pipe 
Interior Wall 
Surface 
Fire Stop 
Assembly 
Horizontal 
Vent Pipe 
Screw
Vent Cap 
(Horizontal 
Termination)
FP1957
HoRIZoNtAl WItH VeRtICAl RISe 
(tHRouGH-tHe-WAll) teRMINAtIoN 
CoNFIGuRAtIoNS
Since it is very important that the venting system main-
tain its balance between the combustion air intake and 
the flue gas exhaust, certain limitations as to vent con-
figurations apply and must be strictly adhered to.
The Vent Graph, showing the relationship between vertical 
and horizontal side wall venting, will help to determine the 
various dimensions allowable. Page 16
Minimum clearance between vent pipes and combus-
tible  materials  is  3"  on  top  and  1"  from  bottom  and 
sides unless otherwise noted (Exception: Outside wall 
with firestop: 1" all around pipes are allowed)
.
When vent termination exits through foundations less than 
0" below siding outcrop, the vent pipe must flush up with 
the siding.
It is best to locate the fireplace in such a way that minimizes 
the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent 
pipe from the flue collar of the fireplace (or the top of the 
transition elbow) to the face of the outer wall or the mount-
ing flange of the termination.