The fireplace must be secured to the floor and/or to framing studs as shown in Figure 6. Use two 
(2) wood screws or masonry/ concrete screws to secure fireplace to the floor. Use four (4) screws 
to attach fireplace to framing. The side nailing flanges are 1/2" or 5/8" to accommodate different 
wall thickness.
Secure FIrepLace to FLoor or FraMInG 
note 
never  install  combustible  materials 
over front face of fireplace.
FP2130
secure fireplace to floor
6”
Framing Members
Noncombustible Material
Noncombustible 
Material Must Rise 
at Least to Top of 
Stand off
Secure to Floor Behind 
Access Panels
All Combustible Materials 
Must Keep 3/4" Spacing
Nailing Flange
FP2130
Figure 6 - 
Secure Fireplace to Floor and Framing Studs 
FInISHInG MaterIaL
note:  Any remote wiring (i.e. remote control, wall switch, and optional fan) must be done prior to 
final finishing to avoid costly reconstruction.
Only noncombustible materials (i.e. brick, tile, slate, steel, or other materials with a UL fire rating of 
Zero) may be used to cover the black painted face of the appliance. It is permissible to bring com-
bustible wall board to the top of the stand-offs on the top and the sides of the unit. A 300°F minimum 
adhesive may be used to attach facing materials to the black surface. If joints between the finished 
wall and the fireplace surround are sealed, a 300°F minimum sealant material (General Electric 
RTV103 or equivalent) must be used.