pre-InStaLLatIon InForMatIon  
FIrepLace LocatIon
Plan for the installation of your appliance. This includes determining where the unit is to be installed, 
the vent configuration to be used, framing and finishing details, and whether any optional accessories 
(i.e. blower, wall switch, or remote control) are desired. Consult your local building code agency to 
ensure compliance with local codes, including permits and inspections.
The following factors should be taken into consideration:
  Clearance to side-wall, ceiling, woodwork, and windows. Minimum clearances to combustibles 
must be maintained.
  This fireplace may be installed along a wall, across a corner, or use an exterior chase. Refer to 
Figure 3 for suggested locations.
  Location should be out of high traffic areas and away from furniture and draperies due to heat 
from appliance.
  Never obstruct the front opening of the fireplace.
  Do not install in the vicinity where gasoline or other flammable liquids may be stored.
  Vent pipe routing. Refer to the Venting section found in this manual for allowable venting con-
figurations.
  These units can be installed in a bedroom. See National Fuel Gas Code ANSI Z233.1/NFPA 54 
— (current edition), the Uniform Mechanical Code — (current edition), and Local Building Codes 
for specific installation requirements.
  These units can be installed in a bathroom. 
Figure 3 - 
Locating Gas Fireplace 
**  Island (C) and room divider (D) installation is possible as long 
as the horizontal portion of vent system (X) does not exceed 
20'. Refer to Installing Horizontal Termination Configuration 
on Page 15.  
When  you  install  your  fireplace  in  (D)  room  divider  or  (E) 
flat on wall corner positions (Y), a minimum of 6" clearance 
must  be  maintained  from  perpendicular  wall  and  front  of 
fireplace. 
Y
E
A
B
C
D
F
Y
X
FP1948
A  Flat on Wall
B  Cross Corner
C  Island**
D  Room Divider*
E  Flat on Wall Corner*
F  Chase Installation
Y  6" Minimum