Monessen Hearth KHLDV400 User Manual

Page of 64
73D0024
15
KHLDV Series Gas Fireplace
VentInG InStaLLatIon 
VertIcaL SIDewaLL InStaLLatIon -
Step 1
Locate vent opening on the wall. It may be necessary to 
first position the fireplace and measure to obtain hole lo-
cation. Depending on whether the wall is combustible or 
noncombustible, cut opening to size. Figure 11 (For com-
bustible walls first frame in opening.)
combustible walls: Cut a 10Z\x”H x 10Z\x”W (267 x 267 
mm) hole through the exterior wall and frame as shown. 
Figure 11
noncombustible walls: Hole opening must be 8Z\x” (216 
mm) in diameter.
VO584-100
Vent Opening
2/99   djt
Vent opening for combustible walls
10Z\x”
(267 mm)
Min.
Fireplace Hearth
Framing Detail
opening for noncombustible wall
8Z\x”
(216 mm)
Fireplace Hearth
FP2293
Figure 11 -  
Locate vent opening on wall
10Z\x”
(267 mm) Min.
Step 2
Secure firestop to the inside frame, center in the 
10Z\x
" x 
10Z\x
" vent opening.
Step 3
Place fireplace into position. Measure the vertical height 
(X) required from the base of the flue collars to the center 
of the wall opening. Figure 12
Step 4
Using appropriate length of pipe section(s) attach to fire-
place with three (3) screws. Follow with the installation of 
the elbow. 
Step 5
Measure the horizontal length requirement figuring a 1Z\v” 
(32 mm) overlap, i.e. from the elbow to the outside wall 
cap. Figure 13
always  install  horizontal  venting  on  a  level 
plane.
X
X
Figure 12 -
Vertical Height 
Requirement
FP1181
X
X
Figure 13 -
Horizontal Length 
Requirement
FP1182
Step 6
Use  appropriate  length    of  pipe  sections  -  telescopic  or 
fixed - and install. 
Sealing  vent  pipe  and  firestop  gaps  with  high  tem-
perature sealant will restrict cold air being drawn in 
around fireplace.
Step 7
Guide  the  vent  terminations  5”  and  8”  collard  into  their 
respective vent pipes. Double check that the vent pipes 
overlap the collars by a minimum of 1Z\v" (32 mm). Secure 
the termination to the wall with screws provided and caulk 
around the wall plate to weatherproof. As an alternative to 
screwing the termination directly to the wall, you may also 
use expanding plugs or an approved exterior construction 
adhesive. 
Support horizontal pipes every 36” (914 
mm) with metal pipe straps.