Monessen Hearth KHLDV400 User Manual

Page of 64
16
73D0024
KHLDV Series Gas Fireplace
VentInG InStaLLatIon 
VertIcaL/HorIZontaL terMInatIon  
conFIGuratIonS
Since it is very important that the venting system main-
tain its balance between the combustion air intake and 
the flue gas exhaust, certain limitations as to vent con-
figurations apply and must be strictly adhered to.
The Vent Graph, showing the relationship between vertical 
and horizontal side wall venting, will help to determine the 
various dimensions allowable. Figure 10 
note: Horizontal sections of this vent system require 
a minimum of 3" clearances to combustibles at the top 
of the flue and 1" clearance at the sides and bottom 
until the flue penetrates the outside wall. a minimum 
1" clearance all around the flue is acceptable at this 
point of penetration. unless the vertical run is 7Z\x feet 
or higher from floor of fireplace, the clearance for the 
horizontal run is 1" on all sides.
Vertical sections of this vent system require a minimum 
of  1"  clearance  to  combustibles  on  all  sides  of  the 
pipe. 
When vent exits through foundations less than 20" below 
outcrop, the termination must be flush up with outcropped 
wall above.
It is best to locate the fireplace in such a way that minimizes 
the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent 
pipe from the flue collar of the fireplace (or the top of the 
Transition Elbow) to the face of the finished outside wall. 
   The  maximum  number  of  90°  elbows  per  side  wall 
installation is three (3). Figure 14 
FP1176
max 90 bends
Figure 14 - 
Maximum Three (3) 90° Elbows Per Installation
3 x 90°
Elbows
24" Min.
FP1176
Max 20"
Max 20"
36"
(914 mm) 
Max.
36"
(914 mm) 
Max.
FP1177
max horizontal run
24”
(610 mm)
FP1177
Figure 15 - 
Maximum Horizontal Run with No Rise
A  10’
B  7’
10’
FP1959
max vent run w/elbows
Figure 16 - 
Maximum Vent Run with Elbows
A + B = 17' Maximum
90° Elbow = 3'
FP1959
   A minimum of 24" is required before a 90° elbow. If a 90° 
elbow is fitted directly after 24" vertical section mounted 
to the top of the fireplace, the maximum horizontal vent 
run before the termination or a vertical rise is 36” (914 
mm). Figure 15
   If a 90° elbow is used in the horizontal vent run (level 
height maintained) the horizontal vent length is reduced 
by 36". Figures 14 and 15. This does not apply if the 
90° elbows are used to increase or redirect a vertical 
rise. Figure 16
example: According to the vent graph (Page 16) the maxi-
mum horizontal vent length in a system with a 10' vertical 
rise is 20’ (6 m) and if a 90° elbow is required in the hori-
zontal vent it must be reduced to 17' (5.2 m). 
In  Figures  16  and  17  dimension A  plus  B  must  not  be 
greater than 17' (5.2 m).