CHECKING GAS PRESSURE
1.   Check gas type. The gas supply must be the same as 
stated on the applianceʼs rating decal. If the gas supply 
is different from the fireplace, STOP! Do not install 
the appliance. Contact your dealer immediately.
2.   Install and attach 30" (762mm) flex line provided with 
on this appliance to 
1
/
2
" gas line.
3.   After completing gas line connection, purge air from 
gas line and test all gas joints from the gas meter to 
the fireplace for leaks. Use a soap and water solution 
or a gas sniffer. 
4.   To adjust flame height, turn HI/LO knob to HI to get 
maximum pressure to burner. Turn HI/LO knob to LO 
to get minimum pressure. 
5.   To check gas pressures at valve, turn captured screw 
counter clockwise 2 or 3 turns and then place tubing to 
pressure gauge over test point. Turn unit to high.  See 
Figure 16. After taking pressure reading, be sure and 
turn captured screw clockwise firmly to reseal. Do not 
over torque. Check test points for gas leaks with a soap 
and water solution or an electronic gas leak detector. 
Do not use open flame to check for 
gas leaks.
W
ARNING
Figure 16 - Gas Pressure Check at Gas Valve 
Pressure 
Test “IN”
Pressure 
Test “OUT”
HI/LO 
Knob
Pilot Adjustment 
Screw