Monessen Hearth DFS42PVC User Manual

Page of 44
18 
71D0532
CHECKING GAS PRESSURE
MILLI-VOLT CONTROL 
(Figure 16)
The valve regulator controls the burner pressure which 
should be checked at the pressure test point.
Turn captured screw counter clockwise two or three 
turns and then place tubing to pressure gauge over 
test point (Use test point “OUT” closest to control 
knob). After taking pressure reading, be sure and turn 
captured screw clockwise firmly to re-seal. Do not 
over torque. Check for gas leaks.
Figure 16 - Pressure Test Point Location
Milli-Volt Control 
When tightening up the joint to the valve, hold the valve securely to prevent movement. 
Test all gas joints from the gas meter to the heater valve for leaks using a gas analyzer or soap and water solution after 
completing connection. DO NOT USE AN OPEN FLAME.
Check the gas pressure with the appliance burning and the control set to HIGH.
Connecting directly to an 
unregulated propane/LPG tank 
can cause an explosion.
W
ARNING
Test Port “OUT”