LX Series Direct Vent Gas Fireplace
FIRepLAce INStALLAtIoN 
checK GAS type
Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install 
fireplace. See dealer where you purchased the fireplace for proper fireplace according to your gas 
type.
INStALLING GAS pIpING to FIRepLAce LocAtIoN
When  using  copper  or  flex  connectors  use  only  fittings 
approved  for  gas  connections.  The  gas  control  inlet  is 
3/8" NPT.
W
ARNING
A qualified installer or service person must 
connect  appliance  to  gas  supply.  Follow 
all local codes.
For  propane/Lp  units,  never  connect 
fireplace directly to the propane/Lp supply. 
this  burner  system  requires  an  external 
regulator (not supplied). Install the external 
regulator between the burner system and 
propane/Lp supply.
INStALLAtIoN IteMS NeeDeD
Before installing fireplace and burner system, make sure you have the items listed below.
  External regulator  
  Piping (check local codes) 
  Sealant (resistant to propane/LP gas) 
 
  (supplied by installer) 
  Test gauge connection* 
•  Sediment trap (recommended)
  Equipment shutoff valve* 
  Tee joint 
  Pipe wrench 
  approved flexible gas line with gas connector (if allowed by local codes — not provided)
A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge 
connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce 
incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not 
reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent 
pointing down as shown in Figure 33. Pointing the vent down protects it from freezing rain or sleet. 
use  only  new  black  iron  or  steel  pipe. 
Internally tinned copper or copper tubing 
can be used per National Fuel code, Section 
2.6.3, providing gas meets hydrogen sulfide 
limits, and where permitted by local codes. 
Gas piping system must be sized to provide 
minimum  inlet  pressure  (listed  on  data 
plate) at the maximum flow rate (Btu/hr). 
undue pressure loss will occur if the pipe 
is too small.
FP1977
external regulator
External 
Regulator 
100 gal. (min) 
Propane/LP 
Supply Tank 
Vent Pointing 
Down
Figure 33 - 
External Regulator with Vent Pointing Down 
(Propane/LP Only)
FP1977
external regulators may be necessary for 
natural  gas.  one-  or  two-pound  systems 
will damage this appliance and may cause 
fire hazard.