Monessen Hearth SWB400I User Manual

Page of 40
26
G
AS
 A
PPLIANCE
 I
NSTALLATION
OPEN POSITION.
BACK REFRACTORY BRICK
SIDE REFRACTORY BRICK
SIDE BRICK
INNER FIREPLACE WRAP
OUTER FIREPLACE WRAP
COMBUSTIBLE MATERIALS 
MAY BE LOCATED AT ZERO
CLEARANCE TO GAS LINE 
BEYOND 4" FROM FIREPLACE SIDE.  
MAINTAIN 1/2" MINIMUM 
AIR SPACE CLEARENCE
TO COMBUSTIBLES FOR
GAS LINE OUT TO 4" FROM
SIDE OF THE FIREPLACE.
GAS LINE ACCESS TUBE
KNOCKOUT
HEARTH BRICK
CAUTION: WHEN USING A GAS
APPLIANCE, THE FIREPLACE
DAMPER MUST BE SET IN FULLY
REPACK INSULATION AROUND GAS LINE WHERE IT PASSES
THRU GAS LINE ACCESS TUBE FOR PROPER SEAL.
F
IGURE
 28
GAS LINE  PLUMBING
The face of your fireplace may be left exposed or trimmed with any noncombustible material such as brick,
stone or marble.  See Figure 29.  If a noncombustible trim is installed, be sure it is fastened snugly to the face
of the fireplace.  A crack between the material and the face of the fireplace could pose a fire hazard and impair
the proper operation of the fireplace.  Blocking the fireplace with framing and attaching the base to the supporting
floor will reduce the possibility of such a crack developing.
CAUTION: Do not allow any trim materials to extend closer than 3/8-inch to the vertical edges of the
firebox opening if you plan to equip the fireplace with glass doors.
Wall ties should be fastened to the face of the fireplace with sheet metal screws and placed in the mortar joints
of masonry trim.
Combustible material must not be installed below the top spacers of the fireplace or overlap the sides
of  the fireplace face.  
See Figures 30 and 31.  Seal the face of the fireplace to the surrounding wall with non-
combustible caulk or trim materials to prevent cold air leakage around the fireplace.
Combustible mantels and combustible trim must be installed in accordance with National  Fire Protection
Association Standard  NFPA 211.  See Figures 30 and 31 for recommendations by fireplace manufacturer.
CAUTION: No trim should block or restrict in any way the flow of air into the air inlets in the face of  the
fireplace.
T
RIM
 I
NSTALLATION
53D9033. Rev 1 03/03