Monessen Hearth DFS32PVC User Manual

Page of 44
40 
71D0532
8'max.
FOR USE OF OPTIONAL AK-4 OUTSIDE AIR KIT
COMBUSTION AIR 
1.  Locate combustion air assembly at an exterior location which is not likely to be accidentally blocked in any manner. 
Locate assembly a min. of 12" above the snow line to prevent blockage by snow accumulation.
2.  Never mount the combustion air inlet assembly in a garage or storage area where combustible fumes such as gasoline 
might be drawn into the fi replace.
3.  Combustion air can be drawn from the crawl space under a house when an adequate supply of air is provided by open 
ventilation.
4.  CAUTION: Do not take combustion air from attic space or garage space.
5.    Locate air supply inlet at least 3' away from any appliance vent terminal. 
6.  Avoid extremely long runs and numerous turns in the duct leading from the fi replace to the combustion air assembly. 
These conditions increase the resistance to the free fl ow of air through the duct. See Figures 40 through 43 for methods 
of installing the outside air for combustion assemblies.
 
Figure 40 - Basement Installation 
Figure 41 - Concrete Slab Installation 
(Optional Outside Air Runs)
Above 
Snow
Level
Ground 
Level 
Basement 
Wall 
Firestop Spacer
Inlet Grill in 
Soffi t
(Overhang)
Figure 43 - 45° Corner Installation on 
Slab Floor 
Figure 42 - Installation Above Basement or 
Crawl Space 
Inside Wall 
Outside
Wall
Duct Extended 
to Miss Joist 
To Outside Wall
Note: Fireplace model in illustrations may not be representative of your appliance.