Designer Series Gas Fireplaces
NoTE : The gas line connection may be made using 
1
/
2
" rigid tubing or an approved flex connector. Since some 
municipalities have additional local codes it is always best to consult your local authorities and the current edition 
of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada CSA-B149 (1 or 2) Installation Code. 
A listed manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 
1
/
8
" NPT pres-
sure tapping point should be installed upstream of the appliance. Figure 36
IMPoRTaNT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is 
for turning on or shutting off the gas to the fireplace. 
Check your building codes for any special requirements 
for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male threads. This will 
prevent excess sealant from going into pipe. Excess seal-
ant in pipe could result in clogged burner system valves.
We recommend that you install a sediment trap/drip leg 
in supply line as shown in Figure 36. Locate sediment trap/drip leg where it is within reach for cleaning. Install 
in piping system between fuel supply and burner system. Locate sediment trap/drip leg where trapped matter 
is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into the 
burner system gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner system may 
not run properly. 
Natural Gas
From Gas Meter 
(4.5" w.c. to 10.5" w.c. Pressure)
Propane/LP
From External Regulator 
(11" w.c. to 13" w.c. Pressure)
3" Minimum
FP1978
gas connection
FIREPLaCE INSTaLLaTIoN 
Figure 36 - 
Gas Connection 
Approved Flexible Gas Line 
CSA Design-Certified Equipment 
Shutoff Valve with 1/8" NPT Tap*
w
a
RNING
only  persons  licensed  to  work  with  gas 
piping  may  make  the  necessary  gas 
connections to this appliance.
C
au
TI
o
N
a  manual  shutoff  valve  must  be  installed 
upstream  of  the  appliance.  union  tee  and 
plugged  1/8”  NPT  pressure  tapping  point 
should be installed upstream of the appliance. 
Figure 35
C
au
TI
o
N
use pipe joint sealant that is resistant to liquid 
petroleum (LP) gas.
Pipe Nipple
Cap
Tee Joint
Sediment Trap/Drip Leg