Monessen Hearth 624DV(ST User Manual

Page of 52
24
42D0200
Designer Series Gas Fireplaces
vENTING INSTaLLaTIoN 
4.  Connect a section of pipe and extend up through the hole.
NoTE: If an offset is needed to avoid obstructions, you must support the vent pipe every three 
(3) feet. use wall straps for this purpose. Refer to Page 23,  Figure 30
. whenever possible, use 
45° elbows instead  of 90° elbows. The 45° elbow offers less restriction to the flow of the flue 
gases and intake air.
5.  Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flash-
ing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the 
flashing. There must be a 1" clearance from the vent pipe to combustible materials.  
6.  Continue to add pipe sections until the height of the vent cap meets the minimum building code 
requirements.
NoTE: you must increase vent height for steep roof pitches. Nearby trees, adjoining roof lines, 
steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high 
winds. Increasing the vent height may solve this problem.
NoTE:  If  the  vent  pipe  passes  through  any  occupied  areas  above  the  first  floor,  including 
storage spaces and closets, you must enclose pipe. you may frame and sheetrock the enclosure 
with standard construction material. Make sure to meet the minimum allowable clearances to 
combustibles. do not fill any of the required clearance spaces with insulation.