WDV Series Gas Fireplace
Flex Vent InstallatIOn
1.  Flexible UL1777 listed venting may be used in any venting application where rigid direct vent components 
can be used. all restrictions, clearances and allowances that pertain to the rigid piping apply to 
the flexible venting.
 Flex kits may not be modified. Flex kits may be 
added to the end of a vent run made of rigid vent sections using pipe 
manufacturer's  approved  flex  to  pipe  adapters.  This  may  occur 
only if doing so does not violate any of the venting length, height, 
routing, horizontal to vertical ratio requirements or clearance 
considerations detailed in this manual.
2.  The flex adapter starter kit (DVF8A/8) is used to attach flex 
venting to the appliance starting collar. It includes 5" inner 
and 8" outer adapter rings. Figure 24
  The inner and outer adapter rings are required to start 
all flex runs.
   Never install damaged or torn flexible venting.
   Over  tightening  clamps  may  rip,  tear,  or  otherwise 
damage flexible venting.
   The adapter kit does not include individual pipe sec-
tions which may be purchased separately. (UL1777 
listed type venting only.)
3.  Start the flexible vent as follows:
A.  Installing the inner flex adapter and pipe. Figure 24
1.  Insert  the  long  side  of  the  5"  inner  ring  into 
exhaust pipe, gently tap to seat into place, and secure with 
screws.
2.  Slide the small gear clamp over the inner flexible vent pipe, 
and push out of the way.
3.  Pull and extend the inner flexible vent.
4.  Slide the inner vent onto the adapter collar, for a minimum 
1
C\v
" overlap.
5.  Locate the clamp at approximately 3/4" from the flex end and tighten.
6.  Secure the clamped inner section with three self-tapping screws, drilled 
equidistant, just above the clamp perimeter.
B.  Installing the outer flex pipe. Figure 24
1.  Firmly insert the 8" outer adapter ring into the outer appliance starting collar 
and secure with screws.
2.  Slide the large gear clamp over the outer flexible vent pipe, and push out 
of the way.
3.  Pull and extend the outer flexible vent.
4.  Slide the outer vent onto the appliance collar outer adapter for a minimum 
1
C\v
" overlap.
5.  Locate the clamp at approximately 3/4" from the flex end and tighten.
6.  Secure the clamped outer section with three self-tapping screws, drilled 
equidistant, just above the clamp perimeter.
C. Routing UL1777 flex pipe.
1.  Always maintain the required clearance when routing the flex vent assembly.
n
O
te
F l e x   v e n t   p i p e   s p a c e r s :   r e f e r   t o 
manufacturer’s  specifications  for  correct 
positioning  of  the  spacer  springs  to 
maintain  proper  distance  between  inside 
and outside pipe.
FP1972
appliance connection
UL1777
Flex Vent
Screws 
(3 places, 
equidistant just 
above gear 
clamp)
1C\v" Flex-
ible Pipe 
and Adapter 
Outer
DVF8A 
Inner Adapter 
Outer Adapter
Appliance 
Starting Collar
Figure 24 - 
Typical Appliance Connection
FP1973
flex pipe bend
UL1777
Flex Vent
5° Radius
Figure 25 - 
Minimum Radius for Flex 
Vent Section
FP1973