WDV Series Gas Fireplace
VentInG InstallatIOn 
InstallatIOn FOr VertIcal terMInatIOn 
1.  Determine the route your vertical venting will take. If 
ceiling joist, roof rafters or other framing will obstruct 
the venting system, consider an offset. Refer to Figure 
20 
to avoid cutting load bearing members. 
For optimal flame appearance, a restrictor disk is necessary 
on straight vertical runs of 10' of more.
  Runs may not incorporate elbows. 
•  
The  disk  is  part  number  56D3027  and  is  included  in 
installation manual packet.
•  
Drop the disk into a 5" inner collar before installing the 
first section of flue or install at the last section before 
installing the termination.
•  
An additional disk may be installed on runs of 35' or more. 
Rotate disks perpendicular to each other. 
nOte: Pay special attention to these installation instructions 
for required clearances (air space) to combustibles when 
passing  through  ceilings,  walls,  roofs,  enclosures,  attic 
rafters, etc. Do not pack air spaces with insulation. Also 
note maximum vertical rise of the venting system and any 
maximum  horizontal  offset  limitations.  Offsets  must  fall 
within the parameters shown in Figures 19 and 20.
2.  Set fireplace in desired location. Drop a line plumb down 
from the ceiling to the position of the flue exit. Mark the 
center point where the vent will penetrate the ceiling. 
Drill a small locating hole a this point. 
  Drop a plumb line from the inside of the roof to the ceiling 
locating hole in the ceiling. Mark the center point where 
the vent will penetrate the roof. Drill a small locating hole 
at this point. 
Flat ceIlInG InstallatIOn
1.  Cut a 10Z\x" (241 mm) square hole in the ceiling using 
the locating hole as a center point The opening should 
be framed to 10Z\x" x 10Z\x" (241 x 241 mm) inside dimen-
sions as shown in Figure 22 using framing lumber the 
same size as the ceiling joist. If the area above the ceil-
ing is an insulated ceiling or a room, nail firestop from 
the top side. This prevents loose insulation from falling 
into the required clearance space. Figure 21. Otherwise, 
install firestop below the framed hole. Figure 22
2.  Assemble the desired lengths of pipe and elbows nec-
essary to reach from the burner system flue up through 
the firestop. Be sure pipe and elbow connections are 
fully twist-locked. 
FP1969
offset w/ wallstrap
Figure 20 - 
Offset with Wall Strap and 45° Elbows 
Roof Flashing 
Wall Strap 
45° Elbows 
Ceiling Firstop 
FP1669
FP1969
firestop w room above
10
1
/
2
"
10
1
/
2
"
FP1970
firestop no room
Figure 21 - If Area Above is a Room, Install Firestop 
above Framed Hole as Shown 
Figure 22 - If Area Above is Not a Room, Install 
Firestop above Framed Hole as Shown 
Firestop 
Nails
Nails
Firestop 
FP1970