CHECK GAS TYPE
Use proper gas type for the fireplace you are installing. If you have conflicting gas types, do not 
install fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas 
type.
INSTALLING GAS PIPING TO FIREPLACE LOCATION
INSTALLATION ITEMS NEEDED
Before installing, make sure you have the items listed below:
•  
External regulator (supplied by installer) 
•  
Tee Joint
•  
Piping (check local codes) 
•  
Pipe wrench
•  
Sealant (resistant to propane/LP gas)
•  
Test gauge connection*
•  
Sediment trap (optional but recommended)
•  
Approved flexible gas line with gas connector (if allowed by 
local codes - not provided)
*A  CSA  design-certified  equipment  shutoff  valve  with  1/8” 
NPT tap is an acceptable alternative to test gauge connec-
tion.  Purchase  the  CSA  design-certified  equipment  shutoff 
valve from your dealer.
For  propane/LP  connections  only,  the  installer  must  supply  an  external  regulator.  The  external 
regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 
11 and 13 inches of water. If you do not reduce incoming gas pressure, burner system regulator 
damage could occur. Install external regulator with the vent pointing down as shown in Figure 14
Pointing the vent down protects it from freezing rain or sleet.
W
ARNING
A  qualified  installer  or  service  person 
must  connect  appliance  to  gas  supply. 
Follow all local codes.
CAUTION
For  propane/LP  units,  never  connect 
fireplace  directly  to  the  propane/LP 
supply. This burner system requires an 
external regulator (not supplied). Install 
the external regulator between the burn-
er system and propane/LP supply.
CAUTION
Use only new black iron or steel pipe. In-
ternally  tinned  copper  or  copper  tubing 
can be used per National Fuel Code, sec-
tion 2.6.3, providing gas meets hydrogen 
sulfide  limits,  and  where  permitted  by 
local codes. Gas piping system must be 
sized to provide minimum inlet pressure 
(listed  on  data  plate)  at  the  maximum 
flow rate (BTU/hr). Undue pressure loss 
will occur if the pipe is too small.
W
ARNING
External  regulators  may  be  necessary 
for natural gas. One- or two-pound sys-
tems  will  damage  this  appliance  and 
may cause fire hazard.
&0
EXTERNAL
External 
Regulator
100 gal. 
(min) Pro-
pane/LP 
Supply 
Tank
Vent 
Pointing 
Down
FP1977
Figure 14 - 
External Regulator with Vent Pointing Down (Pro-
pane/LP Only)
When using copper or flex connectors use only fittings approved for gas connections. The 
gas control inlet is 3/8” NPT.