BBV, SBV Series Natural Vent Gas Fireplaces
FIREPLACE DIMENSIONS & FRAMING
Do  not  fill  spaces  around  firebox  with 
insulation or other materials. This could 
cause a fire.
W
ARNING
316 ” (797 mm)
8”
(203 mm)
14”
(356 mm)
1456O”
(368 mm)
Min. Rough 
Opening
Depth
4056O” (1029 mm)
Min. Rough Opening Width
4” 
B-Vent
1/2” or 5/8”
Drywall 
Spacers
40"
(1016 mm)
34”
(864 mm)
2156O”
(546 mm)
36” (914 mm)
40” (1016 mm)
4056O”
(1029 mm)
Min. Rough
Opening 
Height
1/2" or 5/8" 
Drywall 
Spacers
166M”
(426 mm)
756M”
(184 mm)
26QE”
(56 mm)
96 ”
(244 mm)
436 " (1102 mm)
61
56M
” (1556 mm)
30
6
(778 mm)
43
6
" (1
102 mm)
624037
400BBV dims
6”
(152 mm)
Figure 2 - 
BBV400 Fireplace 
Dimensions and 
Framing
FIREPLACE FRAMING
Firebox framing can be built before or after the appliance is set in place. Construct firebox framing 
following Figures 2 or 3 for your specific installation requirements. Refer to Figures 2 & 3 for firebox 
dimensions. The framing headers may rest on the top of the firebox standoffs.
The firebox may be installed directly on a combustible floor or raised on a platform of an appropri-
ate height. When the firebox is installed directly on carpeting, tile or other combustible material, 
other than wood flooring, the firebox shall be installed on a metal or wood panel extending the full 
width and depth of the enclosure.