Quadra-Fire · Sapphire · 250-7233H
NOTE:
(1) Installation requires a minimum of 11 in. (279mm) 
horizontal run.  Each 1 ft. (305mm) of horizontal vent 
run must include a 1/4 in. (6mm) of vertical rise towards 
the termination.  Never allow the vent to run downward. 
This could cause high temperatures and may present 
the possibility of a house or structure fire.
(2)  The location of the horizontal vent termination on an 
exterior wall must meet all local and national building 
codes, and must not be easily blocked or obstructed, 
see Figure 4.4 on page 9. 
(3)  For installations requiring a vertical rise on the exterior 
of the building, a snorkel kit is available with a 14 in. 
(356mm) and a 36 in. (914mm) tall snorkel termination 
cap.  Follow the same installation procedures as used 
for standard horizontal terminations. If the  snorkel 
termination must be installed below grade (i.e. basement 
application), proper drainage must be provided to 
prevent water from entering the snorkel termination.  Do 
not backfill around snorkel termination.
HOT 
 
WOOD
SCREW
WALL THIMBLE
Step 4. 
Position the horizontal termination cap in the center of the 10 
in. x 10 in. (254mm x 254mm) square hole and run a bead 
of non-hardening mastic around its outside edges, so as to 
make a seal between it and the wall, attach termination cap 
to the exterior wall with the four wood screws provided. The 
arrow on the vent cap should be pointing up (Figure 5.6). 
Figure 5.6
Figure 5.5
Center Line
Wall Thimble
Center Line
Center of H
Center Line
Center Line
Center of Hole
Wall Thimble
When installing the Sapphire in a rear vent configuration with no 
vertical rise: 
a Snorkel Kit must be used, and a derating orifice 
must be installed. The appropriate orifice is supplied with the 
Rear Vent Kit.
45° 
Elbow
14 in. (356mm) Pipe Length
Max. Wall Depth = 
10 in. (254mm)
1 in. (25mm) Clearance from stove 
corner to combustible wall.
1 in. (25mm) Clearanc
from stove corner to 
combustible wall.
Wall Thimble
45° Elbow in Corner Installation
NOTES:
(1)  The four wood screws provided should be replaced with 
appropriate fasteners for stucco, brick, concrete, or 
other types of sidings.
(2)   A termination cap with a built-in vinyl siding standoff is 
highly recommended on a building with vinyl siding. The 
pilot hole will be 2 in. (51mm) closer to the bottom of the 
square than the top. Using a framing square, draw a 14 
in. x 14 in. (356mm x 356mm) square around the pilot 
hole in the siding. See Figure 5.7 on the next page.
Step 3. 
For installations using a round support box/wall thimble 
(check pipe manufacturer's instructions), mark the wall for a 
10 in. x 10 in.  (254mm x 254mm) square hole.  The center 
of the square hole should line up with the center line of the 
horizontal pipe, as shown in Figure 5.5.  Cut and frame the 
hole in the exterior wall where the vent will be terminated.  If 
the wall being penetrated is constructed of noncombustible 
material, i.e. masonry block or concrete, a 7 in. (178mm) 
diameter hole is acceptable.