FLOOR PROTECTION
The floor must be non-combustible material, extending beneath heater and to the front/sides/rear as indicated.  The floor must be a 
minimum of 1/2" thickness ("k" value = 0.84) non-combustible or otherwise adequately protected from radiant heat given off by the unit 
and from sparks and falling embers.  A layer of thin brick or ceramic tile over a combustible floor is not sufficient.  See Alternate Floor 
Protection on page 8.
In USA installations, it is necessary to install a non-combustible floor protector at least 16" in front and 8" to both sides of the fuel loading 
doors.  See *exception below.
In Canada, similar floor protection must be provided 18" (450mm) in front and 8" (200mm) from the sides and rear of the stove.  See 
*exception below.
*EXCEPTION:  Non-combustible floor protections must extend beneath the flue pipe when installed with horizontal venting and extend 
2" (51mm) beyond each side.
Minimum 16" (406mm) from fuel 
loading door
8"
(200mm)
USA
44-7/8"(1140mm) Minimum
39-1/8"
(994mm)
Minimum
 Fuel loading doors
Front
Side
8"
(200mm)
Minimum 16" 
(406mm) from 
fuel loading 
door
CANADA
1371mm
(54")
Minimum
Fuel loading doors
Front
Side
200mm (8")
1295mm (51") Minimum
200mm
 (8")
Mininum 450mm 
(18") from fuel 
loading door.  
Mininum 
450mm 
(18") from 
fuel loading 
door.  
CANADA
200mm (8")
200mm
(8")
450mm (18")
1371mm 
(54")
Minimum
1089mm (42-7/8") Minimum
200mm
(8")
SIDE FUEL DOOR LOCKED SHUT
BOTH FUEL DOORS ACCESSIBLE
16" (406mm) from 
fuel loading door
8"
(200mm)
USA
Front Fuel 
loading door
34-5/8"(879mm) 
Minimum
39-1/8"
(994mm)
Minimum
12”
(305mm)
Minimum
NOTE:  Drawings are for illustration purposes only and are not to scale.
Minimum Hearth Requirements ONLY
See page 6 for stove clearances