Hearth & Home Technologies 8300 User Manual

Page of 43
HearthStone Quality Home Heating Products Inc
                                                                   Champlain 
Model #8300
 
 
22
H
ORIZONTAL 
T
ERMINATION 
V
ENTING 
C
ONFIGURATIONS
 
A minimum of 2’ rise is required (with or without offsets) 
30’ maximum system height (with or without offsets – note shutter setting) 
10’ maximum offset (refer to Figures 8, 9, & 12 – note shutter setting) 
maximum rise to run = 1 to 5 (refer to Figures 8 & 9 – note shutter setting) 
The termination must fall within the area outlined by the shaded area shown in 
Figure 8 and the Chart in Figure 9 should be considered as well. 
Use a vinyl siding stand off when installing against a vinyl siding. 
Horizontal sections require a ¼” rise every 12” of horizontal run. 
For each 90º elbow after the second, remove 5’ from horizontal run. 
At minimum vertical rise, maximum horizontal run is 10’ 
Use with snorkel termination 10’ maximum horizontal run. 
 
 
 
Figure 12. Horizontal Termination
 
 
 
 
 
 
 
 
 
 
Approved DV Venting Configuration for 
Horizontal Termination with: 
 
1.  (1) 90º Elbow & (1) 45º Elbow 
• 
90º Elbow 
• 
45º Elbow 
• 
Straight Pipe 
 
2.  (1) 90º Elbow 
• 
90º Elbow 
• 
Straight Pipe 
 
3.  (2) 90º Elbow 
• 
(2) 90º Elbows 
• 
Straight Pipe 
 
4.  Snorkel 
• 
Snorkel (3 foot) 
• 
Straight Pipe