4100-I  ACT WOOD INSERT
250-7201E
R
FACTORY-BUILT ZERO CLEARANCE FIREpLACE 
(USA iNSTAllATiONS ONlY)
Listed Liner 
Mantel 
SEAL DAMpER AREA OR FACE SEAL
Figure 11A - installation into A Factory Built 
  Zero Clearance Fireplace
The  following  modifications  of  factory  built  fireplaces  are 
permissible:  1) removal of damper;  2) removal of smoke 
shelf or baffle;  ) removal of ember catches;  4) removal 
of fire grate;  5) removal of viewing screen/curtain; and,  6) 
removal of doors. 
 
NOTE:  installation into fireplaces without a permit 
will void the listing.
The factory built chimney must be listed per UL 127 and 
meet the type HT requirements of UL 10.  Factory built 
fireplace chimneys tested to UL 127-1998, may be at the 
fireplace manufacturer’s option, tested to the same criteria 
as UL 10 HT requirements.  If the chimney is not listed 
as  meeting  HT  requirements,  or  if  the  factory  built  fire-
place was tested prior to 1998, a full height listed chimney 
liner must be installed from the appliance flue collar to the 
chimney top.  The liner must meet type HT requirements 
(2100ºF) per UL 1777.  
The liner must be securely attached to the insert flue collar 
and the chimney top.  To prevent room air passage to the 
chimney cavity of the fireplace, seal either the damper area 
around the chimney liner with high temperature sealant or 
the fireplace front with fiberglass batting.
The fireplace must not be altered, except that the damper 
may be removed to accommodate a direct-connect starter 
pipe or chimney liner, and external trim pieces which do 
not affect the operation of the fireplace may be removed 
providing they can be stored on or within the fireplace for 
reassembly if the insert is removed.  
The Quadra-Fire 4100-I  ACT Wood Stove Insert is listed to 
UL 1482 Standard and approved for installation into listed 
factory built zero clearance fireplaces listed to UL 127 con-
forming to the following specifications and instructions:
Minimum Width of cavity opening:
0 in.
Minimum Height:
21 in.
Minimum Depth from front to rear:
16-1/4 in.
The original factory-built clearance fireplace chimney cap 
must  be  re-installed  after  installing  the  approved  chim-
ney liner meeting type H.T. requirements (2100°F) per UL 
1777. The air flow of the factory-built zero-clearance fire-
place system must not be altered. The flue liner top support 
attachment must not reduce the air flow for the existing air-
cooled chimney system.
NOTE:  Refer to chimney liner manufacturer for rec-
ommendations on supporting the liner.
The  permanent  metal  warning  label  provided  must  be 
attached to the back of the fireplace, with screws or nails, 
stating that the fireplace may have been altered to accom-
modate the insert, and must be returned to original condition 
for use as a conventional fireplace.  
If the hearth extension is lower than the fireplace opening, 
the portion of the insert extending onto the hearth must be 
supported.    Manufacturer  designed  adjustable  support  kit 
can be ordered from your dealer.  
(See page 14).
Final approval of this installation type is contingent upon 
the authority having jurisdiction.
Fire Risk.
When lining air-cooled factory-built chimneys:.
•  Run chimney liner approved to UL 1777 Type 
HT requirements (2100 degrees F)
•  Re-install original factory built chimney cap 
ONLY
•  DO NOT block cooling air openings in chimney
•  Blocking cooling air will overheat the chimney
WARNING