Hearth & Home Technologies 4100I-GD-B User Manual

Page of 28
Page 9
 
September 1, 2008
4100-I  ACT WOOD INSERT
250-7201E
R
1.  An outside air inlet must be provided for combustion and must 
remain  clear  of  leaves,  debris,  ice  and/or  snow.    It  must  be 
unrestricted while unit is in use to prevent room air starvation 
which can cause smoke spillage and an inability to maintain a 
fire.  Smoke spillage can also set off smoke alarms.
2.  Unit must be secured to the mobile home structure.   Remove 
bolts from each side of insert and use plumbers tape to secure 
to structure (a washer may be required). Re-install bolts.  
.  Unit must be grounded with #8 solid copper grounding wire or 
equivalent and terminated at each end with N.E.C. approved 
grounding device.
4.  The factory-built fireplace must meet (UM)84-HUD requirements 
for outside combustion air supply to the fireplace fire chamber 
and the chimney must be listed to UL0 HT or a listed UL-1777 
full length six inch (152mm) diameter liner must be used. It must 
be equipped with a spark arrestor cap and the outside air must 
be  installed  on  the  insert. 
(See  Figure  9A  and  installation 
instructions of page 13.)  
5.  Refer to 
page 5 of this manual or the serial number/safety label 
for clearances to combustibles.  The label is located on a beaded 
chain on the left side behind outer skin.
6.  Floor  protections  requirements  on 
page  5  must  be  followed 
precisely.
7.  Use silicone to create an effective vapor barrier at the location were the chimney or other component penetrates to the 
exterior of the structure.
8.  Follow the chimney and chimney connector manufacturer’s instructions when installing the flue system for use in a 
mobile home.
INSTALLATIONS INTO ZERO CLEARANCE 
FIREpLACES IN MOBILE HOMES 
(iN USA ONlY)
WARNING: NEVER DRAW COMBUSTION AIR FROM A WALL, 
FLOOR  OR  CEILING  CAVITY  OR  FROM ANY  ENCLOSED 
SpACE SUCH AS AN ATTIC OR GARAGE.
CAUTION: 
THE  STRUCTURAL  INTEGRITY  OF  THE  MOBILE  HOME 
FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED. 
(i.e., DO NOT CUT THROUgH FlOOR JOiST, WAll STUD, 
CEiliNg TRUSS, ETC.)
WARNING: DO NOT INSTALL IN SLEEpING ROOM.
NOTE:  Offsets from the vertical, not exceeding 45°, are allowed per Section 905(a) of the Uniform Mechanical Code 
(UMC).  Offsets greater than 45° are considered horizontal and are also allowed, providing the horizontal run does 
not exceed 75% of the vertical height of the vent.  Construction, clearance and termination must be in compliance 
with the UMC Table 9C.  This installation must also complies with NFPA 211.
NOTE:  Top sections of chimney must be removable to allow maximum clearance of 1.5 ft. (405cm) from ground level for 
transportation purposes.
9.  Burn wood only.  Other types of fuels may generate poisonous gases (e.g., carbon monoxide).
Spark Arestor Cap
Roof Flashing
Storm Collar
Joist Shield/Firestop
Double Wall 
Connector Pipe 
2. Re-install plate 
1. Remove plate 
Figure 9A - installing Outside Air