Initial Installation
QUALIFIED INSTALLERS ONLY
G
AS
 L
INE
 C
ONNECTION
:
Warning: Only persons licensed to work with gas piping may make the necessary gas connections to 
this appliance.
Gas Line Connection: 
•This fireplace is equipped with a certified flexible pipe located on the right side of the unit, terminating 
in a 3⁄8” male NPT fitting. Consult the local authorities for local codes or use the CAN/CGA B149 (1 or 2) 
installation code in Canada. In the US, gas installations follow either local codes or the current edition of 
the National Fuel Gas Code ANSI Z223.1.
•The efficiency of this unit is a product thermal efficiency rating determined under continuous operating 
conditions and was determined independently of any installed system.
The appliance and its’ shut-off valves must 
be disconnected from the gas supply piping 
system during any pressure testing where 
the pressure exceeds 1⁄2 psig (3.45 KPa) or 
the valve will be damaged.
The  unit  must  be  isolated  from  the  gas 
supply  piping  system  by  closing  its’ 
individual manual shut off valve during any 
pressure  testing  of  the  gas  supply  piping 
system at pressures equal to or less than 
1⁄2 psig (3.45 KPa).
Always check for gas leaks with a soap 
and  water  solution  after  completing 
the required pressure test.
O
L I
T
P
TP
TH
TP
TH
IN
OU
T
H
I
LO
N
OF
O
F
LI
P
T O
��������
�������� ���
�����
�������� ���
������
����
����� ����������
�����
��� �������
����
TO TEST VALVE PRESSURES:
The pressure taps are located on the top right of 
the valve.
•  Turn  set  screw  1  turn  counterclockwise  to 
loosen.
•  Place  5/16  in  (8  mm)  I.D.  hose  over  the 
pressure taps.
•  Check pressures using a manometer.
•  When finished, release pressure, remove hose 
and tighten set screw.
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
Figure 26: Fully Labeled Gas Valve.
Table 4: Pressure and BTU Information.
Main Burner
Natural Gas
(in W.C./KPa)
Propane Gas
(in W.C./KPa)
Orifice:
#38 DMS
#52 DMS
Manifold Press:
3.8 / 0.95
11.0 / 2.74
Min. Manifold Press: 1.1 / 0.27
2.7 / 0.67
Max. Supply Press:
7.0 / 1.74
13.0 / 3.28
Min. Supply Press:
5.0 / 1.24
12.0 / 2.98
Max. BTU Input:
30,000/ 8.8 KW∙h 28,500/ 8.2 KW∙h
Min. BTU Input:
15,000/ 4.4 KW∙h 14,000/ 4.1 KW∙h
19