Enviro Haven Direct Vent Fireplace User Manual

Page of 41
Figure 32. Vent Framing Through Wall/Ceiling.
Figure 31. Vent Pipe Clearances.
2" (51mm)
7
11
/
16
" (195mm)
39"
(991mm)
Initial Installation
QUALIFIED INSTALLERS ONLY
V
ENTING
:
This fireplace has been tested and certified for use with SIMPSON DURAVENT DIRECT VENT TYPE “GS” 
PIPE FOR GAS STOVES, SECURITY CHIMNEY’S SECURE VENT DIRECT VENT SYSTEM kits, AMERICAN 
METAL PRODUCTS AMERIVENT DIRECT and DIRECT-TEMP SELKIRK METALBESTOS.
A 1” (25 mm) clearance to combustibles must be maintained around any vertical vent pipe. Around a 
horizontal vent pipe, the clearance to combustibles should be 2” (51 mm) above and 11⁄2” (38 mm) on 
the sides and bottom. When combustible materials are directly above a 90° elbow, 3 inches (7.6 cm) of 
clearance are necessary (see Figure 31).
Table 6. Vent Pipe Minimum Clearances.
Vertical Pipe to 
the Side Walls
Horizontal Pipe to 
the Sides & Bottom
Above an Elbow 
Above the Unit
Above an Elbow 
Not Above the Unit
Above Horizontal 
Vent Pipe
Wall Frame  8” 
(203mm) or less
Hard 
Pipe
1”
(25.4 mm)
11⁄2”
(38.1 mm)
7
11
/
16
” 
(195mm)
3”
(76.2 mm)
2”
(51 mm)
10”x10”
(25x25cm)
Flex 
Pipe
1”
(25.4 mm)
11⁄2”
(38.1 mm)
7
11
/
16
” 
(195mm)
3 3⁄8”
(86 mm)
3 3⁄8”
(86 mm)
10”x10”
(25x25cm)
A 10” (254 mm) x 10” (254 mm) frame (see Figure 32) will assure the proper support and spacing for 
the vent pipe as it passes through the wall. Installations in Canada require that a wall thimble be used 
for passing through walls and ceilings. All sealing and vapour barriers must comply with local building 
codes.
When planning an installation, it is necessary to select the proper length 
of vent pipe for the particular requirements. The configuration of the 
venting pipes depends on the locations of walls, ceilings and studs. 
However, the pipes cannot be of arbitrary length and arrangement. 
Because the length of the vertical and horizontal sections dramatically 
affects the burning efficiency of the fireplace, certain guidelines have 
been set in I
NITIAL
 I
NSTALLATION
 - V
ENT
 C
ONFIGURATIONS
 
AND
 R
ESTRICTOR
 
S
ETTINGS
.   
Venting terminals can not be recessed into a wall or siding.
WARNING:  This  gas  appliance  must  not  be  connected  to  a 
chimney flue serving a separate solid-burning appliances.
22