Enviro Haven Direct Vent Fireplace User Manual

Page of 41
23
Figure 33. Possible Vent Configurations for Top Vented; Vertical 
and Horizontal Terminations.
1
2
3
4
5
Figure 34. Possible Vent Restrictor Positions.
Initial Installation
QUALIFIED INSTALLERS ONLY
V
ENT
 C
ONFIGURATIONS
 
AND
 R
ESTRICTOR
 S
ETTINGS
:
Figures 33 shows the range of venting options, it shows possible vent configurations if the unit is top 
vented,  for  vertical  and  horizontal  terminations,  any  layout  that  remains  within  the  shaded  area  is 
acceptable. Having the fewest number of elbows is ideal, as they tend to disrupt air movement. Using 
45˚ elbows is preferable to using 90˚ elbows. Also, a shorter vent system will perform better than a 
longer one.
The vent restrictor controls the amount of air moving through the vent pipe. Longer vertical vent lengths 
necessitate  greater  restriction;  position  1  is  open  and  position  5  is  maximum  restriction.  Figure  33 
NOTE: The total length of the vent pipes can 
not exceed 32 feet (15.12 m). Any combination 
of rise and run can be used as long as it lays 
within the shaded area (a total of three (3) 90° 
elbows or six (6) 45° elbows can be used). 
In  addition  to  what  is  shown,  if  a  90° 
elbow  is  used  in  the  horizontal  plane, 
3 feet (91.4 cm) must be subtracted 
from  the  allowable  horizontal  run 
(for  each  45°  elbow,  11⁄2  feet 
must  be  subtracted  from  the 
allowable horizontal run). 
shows the vent restrictor position required, 
relative to the length of vent pipe. The vent 
restrictor  is  located  in  the  center  of  the 
fireplace, above the glass. Figure 34 shows 
the vent restrictor lever and the holes that 
indicate the different levels. To avoid injury, 
it is best to make this adjustment when the 
fireplace is cool or use welder’s gloves or 
oven mitts.
Note:  0,0  in  Figure  33  represents  a  90˚ 
bend directly off the outlet of the unit, 39 
inches (106 cm) from floor, in all horizontal 
instances except when using Selkirk and 
having  less  than  a  4  feet  (1.22  m)  rise 
and  8  feet  (2.44  m)  horizontal  offset.  In 
this case, a 1 foot (30.5 cm) rise must be 
added below the 90˚ bend.