Enviro ENVIRO User Manual

Page of 42
NOTES: 
(1)  If  an  offset  is  necessary  in  the  attic  to  avoid 
obstructions,  it  is  important  to  support  the  vent 
pipe  every  3  feet  (914  mm),  to  avoid  excessive 
stress on the elbows, and possible separation. Wall 
straps  are  available  for  this  purpose  (see  Figure 
41).
(2)  When ever possible, use 45° degree elbows instead 
of 90° degree elbows. The 45° degree elbow offers 
less restriction to the flow of flue gases and intake 
air.
(3)  For  multi  story  installations;  a  ceiling  firestop  is 
required at the second floor, and any subsequent 
floors  (see  Figure  42).  The  opening  should  be 
framed  to  10”  (254  mm)  x  10”  (254  mm)  inside 
dimensions,  in  the  same  manner  as  shown  in 
Figure 35.
(4)  Any occupied areas above the first floor, 
including  closets  and  storage  spaces, 
which  the  vertical  vent  passes  through, 
must be enclosed. The enclosure may be 
framed  and  sheet-rocked  with  standard 
building  materials.  However  consult 
the  appliance  manufactures  installation 
instructions  for  the  minimum  allowable 
clearance between the outside of the vent 
pipe,  and  the  combustible  surfaces  of 
the enclosure. Do not fill any required air 
spaces with insulation.
Figure 41. Use of Wall Straps.
Figure 42. Multi-Story Vent Pipe Installation.
Initial Installation
QUALIFIED INSTALLERS ONLY
28