WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to 
this appliance.  
GAS LINE CONNECTION
•  This  fireplace  is  equipped  with  a  certified  flexible  pipe  located  on  the  right  side  of  the  unit.  This 
flexline is connected to a shut-off ball valve, which terminates in a 3⁄8” female NPT fitting. The ball 
valve can be located on the right or left side of the unit, or where the gas supply can enter through 
the floor of the unit (see Figure 10). Consult your local authorities codes or the CAN/CGA B 149 (1 or 
2) installation code in Canada, or in the USA gas installations follow either local codes or the current 
edition of the National Fuel Gas Code ANSI Z223.1.
•  The  efficiency  rating  of  this  appliance  is  a  product  thermal  efficiency  rating  determined  under 
continuous operating conditions and was determined independently of any installed system.
The appliance and its shutoff valves must be disconnected from 
the gas supply piping system during any pressure testing where 
the pressure exceeds 1⁄2 PSIG (3.45 KPa) or damage will occur 
to the valve.
The  appliance  must  be  isolated  from  the  gas  supply  piping 
system  by  closing  its  individual  manual  shutoff  valve  during 
any  pressure  testing  of  the  gas  supply  piping  system  at  test 
pressures equal to or less than 1⁄2 psig (3.45 KPa).
Always check for gas leaks with a soap and water 
solution  after  completing  the  required  pressure 
test.
TO TEST VALVE PRESSURES
The pressure taps are located on the top right of the valve shown in Figure 45.
• Turn set screw 1 turn counter clockwise to loosen, 
• Place 
5
/
16
” (8 mm) I.D. hose over pressure tap system. 
• Check pressures using a manometer.
• When finished, release pressure, remove hose & tighten set screw.
Natural Gas
Propane
Main Orifice
#40 DMS
#55 DMS
Manifold Pressure
3.8” W.C. (0.95 KPa)
11.0” W.C. (2.74 KPa)
Min. Manifold Pressure
1.2” W.C. (0.28 KPa)
2.7” W.C. (0.67 KPa)
Max Supply Pressure
7.0” W.C. (1.74 KPa)
13.0” W.C. (3.28 KPa)
Min. Supply Pressure
5.0” W.C. (1.25 KPa)
12.0” W.C. (2.98 KPa)
Max BTU/hr Input 29,280 BTU/hr (8.58 KW)
20,590 BTU/hr (6.03 KW)
Min. BTU/hr Input 16,000 BTU/hr (4.69 KW)
10,300 BTU/hr (3.02 KW)
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
O
L I
T
P
TP
TH
TP
TH
IN
OU
T
H
I
LO
N
OF
O
F
LI
P
T O
��������
�������� ���
�����
�������� ���
������
����
����� ����������
�����
��� �������
����
Figure 45. Fully Labeled Gas Valve.
Table 10: Pressure and BTU Information.