Enviro Meridian User Manual

Page of 44
Exhaust Tube
3" (75mm) or 4" (100mm)
"PL" or "L" vent
Wall Thimble
45° Elbow with screen
or Termination Cap
Fresh Air Intake
High Temperature RTV
Silicone Required
Wall framing
Wall thimble
Termination
cap
Vent pipe
Horizontal frame
for thimble
ENVIRO Meridian
•  This  is  due  to  the  back  pressure  in  the 
exhaust  caused  by  airflow  around  the 
structure.
•  All  sections  of  pipe  must  have  three  (3) 
screws  evenly  spaced  and  all  horizontal 
and vertical vent sections located within the 
house must have a bead of high temperature 
silicone installed on the male end of the pipe 
before installation to create a gas tight seal.
• The termination must be 12 inches (30 cm) 
from the outside wall and 12 inches (30 cm) 
above the ground.
• A 45° elbow with a rodent screen may be 
used  in  place  of  the  termination  cap  (or 
stainless steel termination hood). 
Installation
Figure 23: Straight through wall Installation. 
10. The 
pipe  must 
extend  at  least 
12”  (30  cm)  away 
from  the  building. 
If  necessary,  bring 
another  length  of 
pipe  (PL  type)  to 
the  outside  of  the 
home to connect to 
the first section. Do 
not  forget  to  place 
high  temperature 
silicone  around  the 
pipe  that  passes 
through 
the 
thimble.
11. Install  a  vertical 
pipe,  or  if  all 
requirements 
for 
direct 
venting 
are  met,  install 
vent  termination.  The  stainless  steel  cap  termination  manufactured  by  the  vent  manufacturer  is 
recommended. However, when the vent terminates several feet above ground level and there are no 
trees, plants, etc. within several feet, a 45° elbow can be used as termination. The elbow must be 
turned down to prevent rain from entering. 
NOTE:
• Some horizontal through wall installations may require a “T” and 3 to 5 feet (91 to 152 cm) of vertical 
pipe outside the building to help naturally draft in the unit. 
• This may be required if a proper burn cannot be maintained, after the stove has been tested and the 
airflow set. 
Figure 24: Straight through Wall Installation - Side View. 
19