Mitsubishi P96 User Manual

Page of 334
VIII  Test Run Mode ] 
- 149 -
HWE09120
GB
Operation
Outdoor unit model
PUHY-P360TSJMU-A
PUHY-
P96TJMU-A
PUHY-
P120TJMU-A
PUHY-
P144TJMU-A
Operating 
conditions
Ambient 
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor 
unit
No. of connected 
units
Unit
7
No. of units in opera-
tion
7
Model
-
48/48/48/54/54/54/54
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
75 [246-1/16]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
33 [72]
Outdoor 
unit
Electric current
A
86.9
Voltage
V
230
Compressor frequency
Hz
65
74
97
LEV open-
ing
Indoor unit
Pulse
325/325/325/387/387/387/387
SC (LEV1) 
171
171
171
LEV2
2100
2100
2100
Pressure
High pressure (after O/S)/low 
pressure (before accumulator)
MPa
[psi]
2.93/0.86
2.93/0.86
2.93/0.86
[425/125]
[425/125]
[425/125]
Temp. of 
each sec-
tion
Outdoor 
unit
Discharge (TH4)
°C [°F]
74 [165]
73 [163]
82 [180]
Heat exchanger out-
let (TH3)
46 [115]
40 [104]
45 [113]
Accumulator inlet
10 [50]
10 [50]
7 [45]
Accumulator outlet
10 [50]
10 [50]
7 [45]
SCC outlet (TH6)
26 [79]
20 [68]
25 [77]
Compressor inlet
14 [57]
15 [59]
19 [66]
Compressor shell 
bottom
38 [100]
42 [108]
38 [100]
Indoor 
unit
LEV inlet
20 [69]
20 [69]
20 [69]
Heat exchanger  
outlet
10 [50]
10 [50]
10 [50]