Mitsubishi P96 User Manual

Page of 334
VIII  Test Run Mode ]
- 150 -
HWE09120
GB
(2) Heating operation
Operation
Outdoor unit model
PUHY-P312TSJMU-A
PUHY-
P72TJMU-A
PUHY-
P120TJMU-A
PUHY-
P120TJMU-A
Operating 
conditions
Ambient 
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor 
unit
No. of connected 
units
Unit
6
No. of units in opera-
tion
6
Model
-
48/48/48/54/54/54
Piping
Main pipe
m [ft]
5 [16-3/8]
Branch pipe
10 [32-3/4]
Total pipe length
65 [213-1/4]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
34 [75]
Outdoor 
unit
Electric current
A
76.1
Voltage
V
230
Compressor frequency
Hz
53
81
81
LEV open-
ing
Indoor unit
Pulse
406/406/406/414/414/414
SC (LEV1) 
0
LEV2
2100
2100
2100
Pressure
High pressure (after O/S)/low 
pressure (before accumulator)
MPa
[psi]
2.66/0.66
2.66/0.66
2.66/0.66
[387/95]
[387/95]
[387/95]
Temp. of 
each sec-
tion
Outdoor 
unit
Discharge (TH4)
°C [°F]
72 [162]
70 [158]
70 [158]
Heat exchanger out-
let (TH3)
0 [32]
-1 [30]
-1 [30]
Accumulator inlet
0 [32]
-1 [30]
-1 [30]
Accumulator outlet
0 [32]
-1 [30]
-1 [30]
Compressor inlet
0 [32]
-1 [30]
-1 [30]
Compressor shell 
bottom
40 [104]
40 [104]
40 [104]
Indoor 
unit
LEV inlet
36 [97]
36 [97]
36 [97]
Heat exchanger  
inlet
69 [157]
69 [157]
69 [157]