2.  An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected 
(manual address setup for both indoor and outdoor units)
(1) Sample control wiring
(2) Cautions
1)   ME remote controller and MA remote controller cannot 
both be connected to the same group of indoor units.
2)   No more than 2 MA remote controllers can be connected 
to a group of indoor units.
3)   A transmission booster is required in a system to which 
more than 32 indoor units (26 units if one or more indoor 
units of the 72 model or above is connected) are con-
nected.
(3)  Maximum allowable length
1)   Indoor/outdoor transmission line
Same as [5] 1.
2)   Transmission line for centralized control
No connection is required.
3)   MA remote controller wiring
Same as [5] 1.