Mitsubishi P96 User Manual

Page of 334
II  Restrictions ] 
31
- 31 -
HWE09120
GB
(4) Wiring method
1)   Indoor/outdoor transmission line
Same as [5] 1.
Shielded cable connection
Same as [5] 1.
2)   Transmission line for centralized control
No connection is required.
3)   MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the sys-
tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4)   LOSSNAY connection
Connect terminals M1 and M2 on the terminal block 
(TB5) on the indoor unit (IC) to the appropriate terminals 
on the terminal block (TB5) on LOSSNAY (LC). (Non-po-
larized two-wire)
ŒInterlock setting between the indoor units and LOSS-
NAY units must be entered on the remote controller. (Re-
fer to "IV [3] Interlock Settings via the MA Remote 
Controller" or the installation manual for the MA remote 
controller for the setting method.)
5)   Switch setting
Address setting is required as follows.
(5) Address setting method
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
The outdoor units are designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units have 
the same capacity, in the order of address from small to large).
Proce-
dures
Unit or controller
Address 
setting 
range
Setting method
Notes
Factory 
setting
1
Indoor unit
Main 
unit
IC
01 to 50
Assign the smallest ad-
dress to the main unit in the 
group.
To perform a group opera-
tion of indoor units that 
have different functions, 
designate the indoor unit 
in the group with the great-
est number of functions as 
the main unit.
00
Sub unit
Assign sequential numbers 
starting with the address of 
the main unit in the same 
group +1. (Main unit ad-
dress +1, main unit ad-
dress +2, main unit 
address +3, etc.)
2
LOSSNAY
LC
01 to 50
Assign an arbitrary but 
unique address to each of 
these units after assigning 
an address to all indoor 
units.
None of these addresses 
may overlap any of the in-
door unit addresses.
00
3
MA 
remote con-
troller
Main 
remote 
control-
ler
MA
No 
settings re-
quired.
-
Main
Sub 
remote 
control-
ler
MA
Sub 
remote 
controller
Settings to be made ac-
cording to the remote con-
troller function selection
4
Outdoor unit
OC
OS1
OS2
51 to 100
Assign sequential address 
to the outdoor units in the 
same refrigerant circuit.  
The outdoor units are auto-
matically designated as 
OC, OS1, and OS2.(Note)
To set the address to 100, 
set the rotary switches to 
50.
00