Mitsubishi P336 User Manual

Page of 334
VII  Control ]
- 104 -
HWE09120
GB
-6- Compressor Frequency Control 
ŒDepending on the capacity required, the frequency of the compressor is controlled to keep constant evaporation temperature 
(0°C [32°F] = 0.71 MPa [103 psi]) during cooling operation, and condensing temperature (49°C [120°F] = 2.88 MPa [418 psi]) 
during heating operation. 
ŒThe table below summarizes the operating frequency ranges of the inverter compressor during normal operation.
ŒThe OS in the multiple-outdoor-unit system operates at the actual compressor frequency value that is calculated by the OS 
based on the preliminary compressor frequency value that the OC determines.
The maximum frequency during heating operation is affected by the outside air temperature and the dipswitch settings to 
some extent.
(1) Pressure limit
The upper limit of high pressure (63HS1) is preset, and when it exceeds the upper limit, the frequency is decreased every 15 
seconds.
ŒThe actuation pressure is when the high-pressure reading on 63HS1 is 3.58MPa[519psi].
(2) Discharge temperature limit
Discharge temperature (TH4) of the compressor in operation is monitored, and when it exceeds the upper limit, the frequency 
is decreased every minute.
ŒOperating temperature is 115°C [239°F]. 
(3) Periodic frequency control
Frequency control other than the ones performed at start-up, upon status change, and for protection is called periodic frequen-
cy control (convergent control) and is performed in the following manner.
Periodic control cycle
Periodic control is performed after the following time has passed
Œ30 seconds after either compressor start-up or the completion of defrost operation
Œ30 seconds after frequency control based on discharge temperature or pressure limit
The amount of frequency change
The amount of frequency change is controlled to approximate the target value based on the evaporation temperature (Te) and 
condensing temperature (Tc).
Model
Frequency/cooling (Hz)
Frequency/heating (Hz)
Max
Min
Max
Min
72 model 
52
10
67
10
96 model 
65
15
93
15
120 model 
74
15
100
15
144 model 
97
15
120
15