(3) Stopping the defrost operation
ŒThe defrost cycle ends when 12 minutes have passed since the beginning of the cycle, or when the pipe temperature (TH3) 
has been continuously detected for 4 minutes (when SW3-4 is set to OFF) or 2 minutes (when SW3-4 is set to ON) that ex-
ceeds the values in the table below.
ŒThe defrost cycle will not end for two minutes once started unless one of the following conditions is met : Pipe temperature 
reaches 25°C [77°F] and SW3-4 is set to OFF OR 
 =25+TH7°C [77°F+TH7] and SW3-4 is set to ON.
*1 (5°C [41°F] 
 25°C [77°F]).
ŒIn the multiple-outdoor-unit system, defrosting is stopped on all units at the same time. 
(4)  Problems during defrost operation
ŒIf a problem is detected during defrost operation, the operation will be stopped, and the defrost prohibition time based on the 
integrated compressor operation time will be set to 20 minutes.
(5)  Change in the number of operating indoor units during defrost operation
ŒEven when there is a change in the number of operating indoor units during defrost operation, the operation will continue, and 
an adjustment will be made after the completion of the defrost operation.
ŒDefrost operation will be continued, even if the indoor units stop or under the Thermo-OFF conditions until it has run its course.
Model
TH3
SW3 - 4 OFF
SW3 - 4 ON
72 model
10°C [50°F]
5°C [41°F]
96 model
10°C [50°F]
5°C [41°F]
120 model
7°C [45°F]
5°C [41°F]
144 model
7°C [45°F]
5°C [41°F]