Mitsubishi P336 User Manual

Page of 334
IV  Remote Controller ]
- 70 -
HWE09120
GB
[2] Group Settings and Interlock Settings via the ME Remote Controller
1.  Group settings/interlock settings
<Deletion error>
[Normal display]
(B) Interlock Settings 
(A) Group Settings 
   Indoor unit address display window  
Indoor unit 
address 
display window
Interlocked unit 
address 
display window
Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the 
indoor/outdoor unit address.
      (A) Group settings...........Registration of the indoor units to be controlled with the remote controller, 
 
                              and search and deletion of registered information.
      (B) Interlock settings........Registration of LOSSNAY units to be interlocked with the indoor units, 
 
                              and search and deletion of registered information
[Operation Procedures]
(1) Address settings
      Register the indoor unit to be controlled with the remote controller.
          Bring up either one of the following displays on the remote controller:
          The blinking display of   HO,  which appears when the power is turned on, or the
          normal display, which appears when the unit is stopped. The display window must 
          look like one of the two figures below to proceed to the next step.
1
2
     Bring up the   Group Setting   window.
      -Press and hold buttons        [FILTER] and        [LOUVER]  
        simultaneously for 2 seconds to bring up the display as
        shown below.
3
A
C
D
    Select the unit address.
    
Select the address of the indoor unit to be registered by pressing
 
      button 
     [SET TEMP. (    ) or (    )] to advance or go back 
       through the addresses.
    Register the indoor unit whose address appears on the
    display.
    
- Press button      [TEST] to register the indoor unit address
       whose address appears on the display. 
    - If registration is successfully completed, unit type will appear
      on the display as shown in the figure below.
    - If the selected address does not have a corresponding indoor
      unit, an error message will appear on the display. Check the
      address, and try again. 
5
<Successful completion of registration>
 
Unit type (Indoor unit in this case)
         blinks to indicate a registration error.
(Indicates that selected address does not have a 
 corresponding unit.)
4
To register the addresses for multiple indoor units, repeat 
steps      and      above.
3
4
To search for an address, 
go to section (2)  Address Search.
Next page.
To search for an address, 
go to section (2)  Address Search.
 Bring up the   Interlock Setting   window.
 -Press button    [MODE] to bring up the following display. 
  Press again to go back to the  Group Setting  window as shown 
  under step    .
6
G
2
Both the   indoor unit address   and
  interlocked unit address   will be 
displayed together.
Bring up the address of the indoor unit and the address of the 
LOSSNAY to be interlocked on the display.
- Select the address of the indoor unit to be registered by pressing
   button      [SET TEMP. (    ) or (    )] to advance or go back through
   the addresses.   
- Select the address of the LOSSNAY unit to be interlocked by
   pressing button     [TIMER SET (    ) or (    )] to advance or go back
   through the   interlocked unit addresses.
7
8
C
H
Make the settings to interlock LOSSNAY units with indoor 
units.
- Press button       [TEST] while both the indoor unit address and 
   the address of the LOSSNAY units to be interlocked
   are displayed to enter the interlock setting.
- Interlock setting can also be made by bringing up the
   LOSSNAY address in the indoor unit address display
   window and the indoor unit address in the interlocked unit
  address display window.
D
(Displayed alternately)
If registration is successfully 
completed, the two displays as 
shown on the left will appear 
alternately.
If the registration fails,     
will blink on the display.
(Indicates that the selected
 address does not have a
 corresponding unit.)
NOTE :   Interlock all the indoor units in the group with the 
             LOSSNAY units; otherwise, the LOSSNAY units will 
             not operate.
[Blinking display of   HO  ]
ON/OFF 
SET TEMP.
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE
TIMER
FAN SPEED
LOUVER
VENTILATION
AIR DIRECTION
TIMER SET
?
A
F
D
B
H
G
C
E