TechView
Diagnostics View
This window lists the active and inactive (history) diagnostics. There can be 
up to 60 diagnostics, both active and historic. For example, if there were 5 
active diagnostics, the possible number of historic diagnostics would be 55. 
You can also reset active diagnostics here, (i.e., transfer active diagnostics to 
history and allow the chiller to regenerate any active diagnostics).
Resetting the active diagnostics may cause the chiller to resume operation.
The Active and History diagnostics have separate tabs. A button to reset the 
active diagnostics displays when either tab is selected
.
Figure 42  Diagnostic View