Trane RTAC 140-400 ton units (50 HZ) User Manual

Page of 252
118
RTAC-SVX01F-EN
TechView
Configuration View
This view displays the active configuration and allows you to make changes.
 Figure 43
Configuration View
Configuration View allows you to define the chiller's components, ratings, and 
configuration settings. These are all values that determine the required 
installed devices, and how the chiller application is run in the main processor. 
For example, a user may set an option to be installed with Configuration View, 
which will require devices to be bound using Binding View. And when the 
main processor runs the chiller application, the appropriate steps are taken to 
monitor required inputs and control necessary outputs.
Any changes made in the Configuration View, on any of the tabs, will modify 
the chiller configuration when you click on the Load Configuration button 
(located at the base of the window). The Load Configuration button uploads 
the new configuration settings into the main processor.
Any changes made to the configuration will change the unit model number 
number and the confirmation code (CRC). If changes are made to the unit 
configuration the new model number and CRC should be recorded.