Trane PTAC-SVX01C-EN User Manual

Page of 52
16
PTAC-SVX01C-EN
Installation
Notes:
EN = Enabled - operations based on 
other logic
Notes:
N/C = No change from prior state
Step 8. Configure the display 
module settings
Indoor Temperature setpoint
The indoor temperature setpoint 
buttons tell  the unit how warm or 
cool the occupant wants the room.  
The setpoint is set by pressinging the 
up/down buttons  on the interface 
module.  These buttons do not  scroll 
(i.e. holding the button will not 
continue to adjust the setpoint value) 
because each adjustment of the 
setpoint value requires its own 
unique button press.
Default setpoint on first power up: 
72°F (22.0°C – closest approximation)
Setpoint resolution: ± 1°F (± 0.5°C)
User Mode Selection 
Pressing the MODE button on the 
unit tells the unit which mode the 
occupant prefers. There are four 
modes to choose from.
1.
COOL
2.
HEAT
3.
FAN (fan only)
4.
OFF (default for first power up)
Table 8.
 Output settings
User Mode / Model
ID 
Fan 
High
ID 
Fan 
Low
Aux 
Heat Comp
Rev 
Valve 
(PTHE)
 OD 
Fan
Rmt 
Fan
Cond 
Pump 
(PTHE)
Vent 
Door
/Fan
High Heat Pump 
(PTHE only)
ON
OFF
OFF
ON
OF
ON
EN
EN
EN
Low Heat Pump 
(PTHE only)
OFF
ON
OFF
ON
OFF
ON
EN
   EN
EN
High Emergency/
Auxiliary Heat
ON
OFF
ON
OFF
N/C
OFF
EN
   EN
EN
Low Emergency/
Auxiliary Heat
OFF
ON
ON
OFF
N/C
OFF
EN
   EN
EN
High Cooling
ON
OFF
OFF
ON
ON
ON
EN
   EN
EN
Low Cooling
OFF
ON
OFF
ON
ON
ON
EN
   EN
EN
High Fan
ON
OFF
OFF
OFF
N/C
OFF
EN
   EN
EN
Low Fan
OFF
ON
OFF
OFF
N/C
OFF
EN
   EN
EN
Off
OFF
OFF
OFF
OFF
N/C
OFF
OFF
   EN
OFF
Fan Speed Selection 
Pressing the FAN button on the 
interface module determines fan 
speed.  There are  two fan speeds to 
choose from.
1.
LOW   (default for first power up)
2.
HIGH
Field commissioning support
Manual  Test Mode
A manual test mode is provided to 
allow a field technician to verify 
proper output and end device 
operation through a predetermined, 
timed sequence.  
Figure 16.
Digital display module
Fan
Mode
The sequence will automatically 
advance through all outputs and exit 
when the sequence has completed; it 
is left to the technician to monitor the 
status of the end devices during the 
test to verify that each operates 
properly.  
Manual test is initiated by combining 
the following conditions:
User Mode = OFF
Press and hold MODE & 
SETPOINT DOWN for 5 seconds
During the test process, the word 
"STEP" and the corresponding step 
number will be lighted on the 
display.  After the final step has been 
executed, the controller will exit 
Manual test and force the controller 
to into a reset.
Manual test mode may be cancelled 
by pressing any button on the 
display.
Manual test is not available if there is 
no interface module, as is in Class 2 
control applications.
The test sequence attempts to clear 
unit diagnostics and restore normal 
unit operation prior to testing the 
outputs.  If the diagnostics remain 
after an attempt to clear them, 
manual test may be affected or 
disallowed.
Dehumidification
The PTAC controller does not directly 
measure room humidity. 
The PTAC provides dehumidfication 
by combining the following actions 
in a predefined sequence.
1.
The PTAC subcools the room to a 
preset state, a dehumidification 
offset below the cooling setpoint. 
2.
The unit will automatically adjust 
the fan speed.
3.
When incorporating the vent 
door option, the controller will 
automatically adjust its position.