Trane PTAC-SVX01C-EN User Manual

Page of 52
PTAC-SVX01C-EN
17
Installation
Step 9. Programmable 
Settings
The controller has a total of six (7) 
parameters that are user-
configurable:
1.
Vent Door Configuration
2.
Indoor Fan Cycle configuration
3.
Temperature Setpoint Limiting 
configuration
4.
Energy Management Setpoint 
Offset configuration
5.
Display Units configuration
6.
Indoor  Temperature Calibration
7.
DH Offset
The interface module texts 
“SETTING” and “STEP” provide user 
feedback when the unit is in the 
configuration mode.  The number 
directly above the word “STEP” 
indicates the configuration step that 
is being adjusted.  The numbers 
above the word “SETTING” (XX.x) 
indicate the value of the parameter.  
In order for the user to access the 
configurable parameters, a digital 
display module must be present.  
The configuration set-up mode is 
entered by pressing and holding the 
"MODE" and "FAN" buttons 
simultaneously for 5 seconds.
Table 9.
 Set point configuration
Configuration 
step
Step description
Configuration 
setting
Setting description
1
Ventilation Enable 0
1 (default)
Ventilation is disabled
Ventilation is enabled
2
Indoor fan cycle
0 (default)
Cycle with compressor
continuously, OFF in OFF mode
ON continuously, HIGH in OFF 
mode
1
2
3
Temperature 
Setpoint Limits
0 (default)
cool 50 - 90°F, heat 50 - 90°F
1
cool 55 - 90°F, heat 50 - 85°F
2
cool 60 - 90°F, heat 50 - 80°F
3
cool 65 - 90°F, heat 50 - 75°F
4
Energy 
Management 
Default: 10°F (5.5°C)
Range: 0 to 20°F 
 (0.0 to 10.0°C)
Resolution: 1.0°F 
 (0.5°C)
5
Display units
0 (default)
IP (English)
1
SI  (Metric)
6
Indoor 
Temperature 
Calibration
Default: 0°F (0.0°C)
Range: -9 to 9°F 
 (-5.0 to 5.0°C)
Resolution: 1.0°F
(0.5°C)
7
DH offset 
Default: 1°F (0.5°C)
Range: 0 to 2°F
 (0.0 to 1.0°C)
Resolution 1.0°F 
Value of zero disables DH.
 (0.5°C)