Sequence of Operation
The Simplicity Control will stage off the cooling as 
follows:
  If the space temperature is within 0.5° F of the 
“CV OCCUPIED COOLING SETPOINT” or 
“CV UNOCCUPIED COOLING SETPOINT” 
the control turns off the System 2 compressors, 
if on, with a 30 second delay between the com-
pressors provided the minimum compressor run 
times have been satisfi ed.
  If the space temperature is equal to or below the 
“CV OCCUPIED COOLING SETPOINT” or 
“CV UNOCCUPIED COOLING SETPOINT” 
the control turns off the System 1 compressors 
with a 30 second delay between the compressors 
provided the minimum compressor run times 
have been satisfi ed.
The Simplicity Control has the following timing cooling 
functions:
  Minimum off time of 5 minutes.
  Minimum on time of 3 minutes – This param-
eter can be programmed from between 1 and 10 
minutes using the COOLING SETUP tab of the 
in the Simplicity PC software package.
Heating Operation – Occupied or Unoccupied
The Simplicity Control will stage on the heat as 
follows:
  When the space temperature is 1.5° F – 1.9° F 
below the “CV OCCUPIED HEATING” or “CV 
UNOCCUPIED HEATING SETPOINT”
 the 
control energizes the fi rst stage of heat.
  When the space temperature is 2.0° F – 2.4° F 
below the “CV OCCUPIED HEATING” or “CV 
UNOCCUPIED HEATING SETPOINT”
 the 
control energizes the second stage of heat. 
  When the space temperature is 2.5° F or more 
below the “CV OCCUPIED HEATING” or “CV 
UNOCCUPIED HEATING SETPOINT”
 the 
control energizes the third stage of heat.
The Simplicity Control will stage off the heat as 
follows:
  When the space temperature is 2.4° F below the 
“CV OCCUPIED HEATING” or “CV UNOC-
CUPIED HEATING SETPOINT”
 the third stage 
of heating will turn off.
  When the space temperature is 1.9° F below the 
“CV OCCUPIED HEATING” or “CV UNOC-
CUPIED HEATING SETPOINT”
 the second 
stage of heat will turn off.
  When the space temperature is 0.1° F above the 
“CV OCCUPIED HEATING” or “CV UNOC-
CUPIED HEATING SETPOINT”
 the fi rst stage 
of heating will turn off.
The Simplicity Control has the following heating timing 
functions:
  A minimum off time of 2 minutes.
  A minimum on time of 3 minutes.
  There is a 30 second time delay between stag-
es.
Stand Alone
The following System Parameters must be programmed 
through the Simplicity Control:
  “CV OCCUPIED COOLING SETPOINT” – us-
ing Parameter 10 under the PROGRAM key on 
the Simplicity control board or under the COOL-
ING SETUP tab in the Simplicity PC software 
package.
  “CV OCCUPIED HEATING SETPOINT” – us-
ing Parameter 11 under the PROGRAM key on 
the Simplicity control board or under the HEAT-
ING SETUP tab in the Simplicity PC software 
package.
  “CV UNOCCUPIED COOLING SETPOINT” 
– using Parameter 12 under the PROGRAM 
key on the Simplicity control board or under 
the COOLING SETUP tab in the Simplicity PC 
software package.