York YPAL 051 User Manual

Page of 168
68
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
Sequence of Operation
The Simplicity Control will stage off the heat as 
follows:
  When the return air temperature is 2.4° F below 
the “CV OCCUPIED HEATING” or “CV UN-
OCCUPIED HEATING SETPOINT”
 the third 
stage of heating will turn off.
  When the return air temperature is 1.9° F below 
the “CV OCCUPIED HEATING” or “CV UN-
OCCUPIED HEATING SETPOINT”
 the second 
stage of heat will turn off.
  When the return air temperature is 0.1° F above 
the “CV OCCUPIED HEATING” or “CV UN-
OCCUPIED HEATING SETPOINT”
 the fi rst 
stage of heating will turn off.
The Simplicity Control has the following heating timing 
functions:
  A minimum off time of 2 minutes.
  A minimum on time of 3 minutes.
  There is a 30 second time delay between stag-
es.
VARIABLE AIR VOLUME (VAV)
A Variable Air Volume (VAV) unit can be controlled 
by four methods:
 Stage 
thermostat
 Communicated 
Space 
Temperature
 Hardwired 
Space 
Temperature
 Stand 
Alone 
Return 
Air 
Temperature
Cooling - Occupied with Thermostat
The following System Parameters must be programmed 
through the Simplicity Control for VAV operation:
  “VAV COOLING SUPPLY AIR TEMP UPPER   
SETPOINT” – using Parameter 23 under the 
PROGRAM key on the Simplicity control board 
or under the COOLING SETUP tab in the Sim-
plicity PC software package.
  “VAV COOLING SUPPLY AIR TEMP LOWER   
SETPOINT” – using Parameter 24 under the 
PROGRAM key on the Simplicity control board 
or under the COOLING SETUP tab in the Sim-
plicity PC software package.
The Simplicity Control initiates compressor operation 
as follows:
  The Simplicity Control will turn compressors on 
and off based of the difference between the sup-
ply air temperature and the cooling set point.  
  With no thermostat call or a Y1 first stage 
call the Simplicity Control will control to the 
“VAV COOLING SUPPLY AIR TEMP UPPER 
SETPOINT”
.  The Y1 input is not required to 
initiate compressor operation. 
  When there is a Y2, Y3, or Y4 call from the 
thermostat the Simplicity Control will control to 
the  “VAV COOLING SUPPLY TEMP LOWER 
SETPOINT”
.
  The control uses a 5-degree dead band around 
the cooling “VAV COOLING SUPPLY TEMP 
UPPER   SAT SETPOINT”
 or “VAV COOLING 
SUPPLY AIR TEMP LOWER SETPOINT”.
  When the supply air temperature is 5.0° F 
or more above the cooling “VAV COOLING 
SUPPLY TEMP UPPER SAT SETPOINT” 
or 
“VAV COOLING SUPPLY AIR TEMP LOWER 
SETPOINT”
 the Simplicity Control will energize 
the fi rst compressor.
  The control records the supply air temperature 
right before the compressor is turned on and 
compares it to the supply air temperature after 5 
minutes of operation.
  A second compressor will be turned on if both of 
the following criteria are met:
–  The supply air temperature is still 5.0° F or 
more above the “VAV COOLING SUPPLY 
TEMP UPPER   SAT SETPOINT”
 or “VAV 
COOLING SUPPLY AIR TEMP LOWER 
SETPOINT”
.