York YPAL 051 User Manual

Page of 168
71
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
5
Occupied Cooling – Stand Alone
The following System Parameters must be programmed 
through the Simplicity Control for VAV Stand Alone 
operation:
•  “VAV COOLING SUPPLY AIR TEMP UP-
PER   SETPOINT” – using Parameter 23 under 
the PROGRAM key on the Simplicity control 
board or under the COOLING SETUP tab in the 
Simplicity PC software package.
•  “VAV COOLING SUPPLY AIR TEMP LOWER   
SETPOINT” – using Parameter 24 under the 
PROGRAM key on the Simplicity control board 
or under the COOLING SETUP tab in the Sim-
plicity PC software package.
•  “VAV SUPPLY AIR TEMP RESET SETPOINT” 
– using Parameter 25 under the PROGRAM 
key on the Simplicity control board or under 
the COOLING SETUP tab in the Simplicity PC 
software package.
•  “SPACE SENSOR FAULT OVERRIDE EN-
ABLED” must be turned on – using Parameter 
8 under the PROGRAM key on the Simplicity 
control board or under the SYSTEM OPTIONS 
tab in the Simplicity PC software package. 
The Simplicity Control will control the operation of the 
compressors as follows:
•  If the return air temperature is 2.0° F or more 
above the “VAV SUPPLY AIR TEMP RESET 
SETPOINT” the control will use the “VAV 
COOLING SUPPLY AIR TEMP LOWER 
SETPOINT”.
•  If the return air temperature is not 2.0° F or 
more above the “VAV SUPPLY AIR TEMP 
RESET SETPOINT” the control will use the 
“VAV COOLING SUPPLY AIR TEMP UPPER 
SETPOINT”.
•  If the control is using the “VAV COOLING 
SUPPLY AIR TEMP LOWER SETPOINT” per 
above the return air temperature must be equal 
to or less than the “VAV SUPPLY AIR TEMP 
RESET SETPOINT” before the control would 
switch to the “VAV COOLING SUPPLY AIR 
TEMP UPPER SETPOINT”.
•  The control uses a 5-degree dead band around the 
cooling “VAV COOLING SUPPLY AIR TEMP 
UPPER SETPOINT” or “VAV COOLING SUP-
PLY AIR TEMP LOWERT SETPOINT”.
•  When the supply air temperature is 5.0° F or more 
above the cooling “VAV UPPER COOLING SAT 
SETPOINT” or “VAV LOWER COOLING SAT 
SETPOINT” the Simplicity Control will energize 
the fi rst compressor.
•  The control records the supply air temperature 
right before the compressor is turned on and 
compares it to the supply air temperature after 5 
minutes of operation.
•  A second compressor will be turned on if both of 
the following criteria are met:
–  The supply air temperature is still 5.0° F or 
more, greater then the “VAV UPPER COOL-
ING SAT SETPOINT” or “VAV LOWER 
COOLING SAT SETPOINT”.
–  The Simplicity Control uses the temperature 
difference calculated when the fi rst compres-
sor was turned on to verify the supply air tem-
perature will not drop 5.0° F or more below 
the cooling “VAV UPPER COOLING SAT 
SETPOINT” or “VAV LOWER COOLING 
SAT SETPOINT”.  If turning on a compressor 
would result in the specifi ed drop in supply 
air temperature, the second compressor will 
not be turned on.
•  The same logic will be used to stage on compres-
sor 3 and 4.
The Simplicity Control turns off compressor operation 
as follows:
•  The supply air temperature is 5.0° F or more 
below the ““VAV COOLING SUPPLY TEMP 
UPPER SAT SETPOINT” or “VAV COOLING 
SUPPLY AIR TEMP LOWER SETPOINT”. 
•  It has been more than 5-minutes since the last 
compressor was turned on.
•  The compressors will be turned off in the reverse 
order they were turned on.