Sequence of Operation
  When the supply air temperature is 5.0° F or more 
above the cooling “VAV UPPER COOLING SAT 
SETPOINT”
 or “VAV LOWER COOLING SAT 
SETPOINT”
 the Simplicity Control will energize 
the fi rst compressor.
  The control records the supply air temperature 
right before the compressor is turned on and 
compares it to the supply air temperature after 5 
minutes of operation.
  A second compressor will be turned if both of 
the following criteria are met:
–  The supply air temperature is still 5.0° F or 
more, greater then the “VAV UPPER COOL-
ING SAT SETPOINT”
 or “VAV LOWER 
COOLING SAT SETPOINT”
.
–  The Simplicity Control uses the temperature 
difference calculated when the fi rst compres-
sor was turned on to verify the supply air tem-
perature will not drop 5.0° F or more below 
the cooling “VAV UPPER COOLING SAT 
SETPOINT”
 or “VAV LOWER COOLING 
SAT SETPOINT”
.  If turning on a compressor 
would result in the specifi ed drop in supply 
air temperature, the second compressor will 
not be turned on.
  The same logic will be used to stage on compres-
sor 3 and 4.
The Simplicity Control turn off compressor operation 
as follows:
  The supply air temperature is 5.0° F or more 
below the ““VAV COOLING SUPPLY TEMP 
UPPER SAT SETPOINT” 
or “VAV COOLING 
SUPPLY AIR TEMP LOWER SETPOINT”
. 
  It has been more than 5-minutes since the last 
compressor was turned on.
  The compressors will be turned off in the reverse 
order they were turned on.
Cooling – Unoccupied with a Hard Wired or Com-
municated Space Sensor 
The Simplicity Control cannot operate unoccupied 
cooling with this method of control.
Heating – Occupied with a Hard Wired or Com-
municated Space Sensor
The following parameter must be programmed into the 
Simplicity Control:
  “VAV OCCUPIED HEATING ENABLED” – This 
must be turned on using Parameter 26 under the 
PROGRAM key on the Simplicity control board 
or under the HEATING SETUP tab in the Sim-
plicity PC software package.
  “MORNING WARM-UP/ VAV RETURN AIR 
TEMP SETPOINT” – using Parameter 29 under 
the PROGRAM key on the Simplicity control 
board or under the HEATING SETUP tab in the 
Simplicity PC software package.
  “VAV OCCUPIED HEATING SETPOINT” – us-
ing Parameter 27 under the PROGRAM key on 
the Simplicity control board or under the HEAT-
ING SETUP tab in the Simplicity PC software 
package.
The unit will initiate Occupied Heating when the 
following criteria is met:
  The space temperature is 2.0° F less than the 
“VAV OCCUPIED HEATING SETPOINT”.
  The return air temperature is 0.1° F below the 
“MORNING WARM UP / VAV RETURN AIR 
TEMP SETPOINT”
.
The unit will terminate Occupied Heating when the:
  The return air temperature is equal to the 
“MORNING WARM UP RAT SETPOINT”.
The “VAV OCCUPIED HEATING SETPOINT” should 
always be set below the “MORNING WARM UP RAT 
SETPOINT”
.
Heating – Unoccupied with a Hard Wired or Com-
municated Space Sensor
The Simplicity Control cannot operate unoccupied 
heating with this method of control.