York YPAL 051 User Manual

Page of 168
83
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
5
  The Simplicity Control will monitor the supply 
air temperature and compare it to the “SUPPLY 
AIR TEMP LIMIT COOLING SETPOINT”
.  If 
the supply air temperature is 0.1° F or more below 
this value and the compressor minimum run time 
requirement has been met the Simplicity Control 
will turn off the compressor.
  The Simplicity Control then starts a 10-minute 
timer.
  If after 10 minutes the supply air temperature is 
equal to or greater than the “SUPPLY AIR TEMP 
LIMIT COOLING SETPOINT”
 plus 5.1° F the 
Simplicity Control will turn the compressor back 
on provided there is still a demand for the staged 
off compressor.
  If after 10 minutes the supply air temperature is 
not less than the “SUPPLY AIR TEMP LIMIT 
COOLING SETPOINT”
 plus 5.1° F Simplic-
ity Control will keep the compressor off until 
the supply air temperature is equal to or greater 
than the “SUPPLY AIR TEMP LIMIT COOLING 
SETPOINT”
 plus 5.1° F.  The Simplicity Control 
will then turn the compressor back on provided 
there is still a demand for the staged off compres-
sor.
If multiple compressors are energized the control will 
monitor the supply air temperature and respond as 
follows:
  The Simplicity Control will monitor the supply 
air temperature and compare it to the “SUPPLY 
AIR TEMP LIMIT COOLING SETPOINT”.
  If 
the supply air temperature is 0.1° F or more below 
this value and the compressor minimum run time 
requirement has been met the Simplicity Control 
will turn off the compressor with the shortest run 
time.
  The Simplicity Control starts a 10 minute and 3 
minute timing sequence.
  If after 3 minutes, the supply air temperature 
is still 0.1° F below the “SUPPLY AIR TEMP 
LIMIT COOLING SETPOINT”
 the control will 
turn off the next compressor with the shortest run 
time.
  The Simplicity Control will continue to turn 
off compressors every 3 minutes until the sup-
ply air temperature is equal to or greater than 
the  “SUPPLY AIR TEMP LIMIT COOLING 
SETPOINT”.
  If after 10 minutes the supply air temperature 
is equal to or greater than the “SUPPLY AIR 
TEMP LIMIT COOLING SETPOINT”
 plus 5.1° 
F the Simplicity Control will turn the staged off 
compressor(s) back on provided there is still a 
demand for the use of the staged off compres-
sor.
  If after 10 minutes the supply air temperature is 
not less than the “SUPPLY AIR TEMP LIMIT 
COOLING SETPOINT”
 plus 5.1° F the Simplic-
ity Control will keep the compressor(s) off until 
the supply air temperature is equal to or greater 
than the “SUPPLY AIR TEMP LIMIT COOLING 
SETPOINT” 
plus 5.1° F. The Simplicity Control 
will then turn the compressor(s) back on provided 
there is still a demand for the staged off compres-
sor.
Heating
T h e   f o l l o w i n g   S y s t e m   P a r a m e t e r s   m u s t   b e 
programmed:
“SUPPLY AIR TEMP LIMIT FOR HEATING 
ENABLED”
- must be enabled using Parameter 16 under 
the PROGRAM key on the Simplicity control board or 
under the HEATING SETUP tab in the Simplicity PC 
software package.
“SUPPLY AIR TEMP LIMIT HEATING SETPOINT” 
– Using Parameter 17 under the PROGRAM key on the 
Simplicity control board or under the HEATING SETUP 
tab in the Simplicity PC software package.
If a single heat stage is on the control will monitor the 
supply air temperature and respond as follows:
  The Simplicity Control will monitor the supply 
air temperature and compare it to the “SUPPLY 
AIR TEMP LIMIT HEATING SETPOINT”.
  If the 
supply air temperature is 0.1° F or more above 
this value and the heat stage minimum run time 
has been met the Simplicity Control will turn off 
the heat stage.