JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
Sequence of Operation
  The Simplicity Control then starts a 3 minute 
timer.
  If after 3 minutes the supply air temperature is 
equal to or less than the “SUPPLY AIR TEMP 
LIMIT HEATING SETPOINT”
 minus 10.1° F the 
Simplicity Control will turn the heat stage back 
on provided there is still a demand for the staged 
off heat stage.
  If after 3 minutes the supply air temperature is 
not equal to or less than the “SUPPLY AIR TEMP 
LIMIT HEATING SETPOINT”
 minus 10.1° F the 
Simplicity Control will keep the heat section off 
until the supply air temperature is equal to or less 
than the “SUPPLY AIR TEMP LIMIT HEATING 
SETPOINT”
 minus 10.1° F.  The Simplicity Con-
trol will turn the heat stage back on provided there 
is still a demand for the staged off heat stage.
If multiple heat stages are on the control will monitor 
the supply air temperature and respond as follows:
  The Simplicity Control will monitor the supply 
air temperature and compare it to the “SUPPLY 
AIR TEMP LIMIT HEATING SETPOINT”.
  If the 
supply air temperature is 0.1° F or more above 
this value and the heat stage minimum run time 
requirement has been met the Simplicity Control 
will turn off the heat section with the shortest run 
time.
  The Simplicity Control starts a 3 minute and 
30 second timing sequence. If after 30 seconds 
the supply air temperature is still 0.1° F above 
the  “SUPPLY AIR TEMP LIMIT HEATING 
SETPOINT”
, the control will turn off the next 
heat stage with the shortest run time.
  The Simplicity Control will continue to turn off 
heat stages every 30 seconds until the supply air 
temperature is equal to or less than the “SUPPLY 
AIR TEMP LIMIT HEATING SETPOINT”.
  If after 10 minutes the supply air temperature is 
equal to or less than the “SUPPLY AIR TEMP 
LIMIT HEATING SETPOINT”
 minus 10.1° F 
the Simplicity Control will turn the heat stage(s) 
back on provided there is still a demand for the 
use of the staged off heat stage.
  If after 10 minutes the supply air temperature 
is still greater than the “SUPPLY AIR TEMP 
LIMIT HEATING SETPOINT”
 minus 10.1° F the 
Simplicity Control will keep the heat stage(s) off 
until the supply air temperature is equal to or less 
than the “SUPPLY AIR TEMP LIMIT HEATING 
SETPOINT”
 minus 10.1° F. The Simplicity Con-
trol will turn the heat stage(s) back on provided 
there is still a demand for the staged off heat 
stage.
SPACE SENSOR WITH SET POINT ADJUSTMENT
A space sensor with a 20 K ohm slide potentiometer 
can be used to reset the Occupied Cooling and Heating 
set points.
In addition to the use of a space sensor with the 
slide potentiometer the following parameter must be 
programmed:
“SPACE TEMPERATURE OFFSET RANGE” – The 
offset range must be programmed using Parameter 
56 under the PROGRAM key on the Simplicity Elite 
control board or under the SYSTEMS OPTIONS tab 
in the Simplicity Elite software package.
Sequence of Operation
As the slide potentiometer is moved the Occupied 
Cooling and Heating set point is changed based on 
the programmed “SPACE TEMPERATURE OFFSET 
RANGE”
.  The “SPACE TEMPERATURE OFFSET 
RANGE”
 can be set from 0 to 5.0° F.  For example, 
if the “SPACE TEMPERATURE OFFSET RANGE” 
is programmed for 3.0° F and the resistance of the 
potentiometer is lowered the Cooling and Heating set 
points would be lowered up to 3.0° F.  If the resistance 
is increased the Cooling and Heating set points would 
be increased up to 3.0° F.