FORM 115.20-NOM6 (1106)
INSTALLATION
RECEIVING
Material in this shipment has been inspected at the 
factory and released to the transportation agency in 
good condition. When received, a visual inspection of 
all cartons should be made immediately. Any evidence 
of rough handling or apparent damage should be noted 
on the delivery receipt and the material inspected in 
the presence of the carrier’s representative.
STORAGE
If the equipment is not to be immediately installed, 
store it in a dry location with the motor protected 
against moisture, dust, corrosion and physical damage.  
If units are to be stored for six months or longer, see 
long term storage requirements (Form 50.20-NM3).
DESCRIPTION
The YCW  models  are  available  as  2-pipe  cooling 
(YCW), 2-pipe cooling with electric heat (YCWE) 
and a 4-pipe heating/cooling (YCW-HW). All units are 
provided with a 3-speed fan control in the control box 
in the fan section (left side), with 24v access on the top 
panel, left. Manual and auto changeover thermostats 
and the T200 auto speed control thermostats can be 
used with this unit.  Twenty-four volt (24 v) power is 
provided in the unit for thermostat operation.
The 2-pipe cooling unit is provided with a single coil 
with connections on the top panel, right side.
The  2-pipe  cooling  with  electric  heat  is  provided 
with a single chilled water coil and electric heat ele-
ments; coil connections are on the top panel, right 
side; electrical connections are on the top panel, left 
side and the units are provided with a disconnect on 
the front panel.
The 4-pipe heating/cooling unit is provided with 2 
coils with single end sheets – cooling connections are 
on the top panel, right side and the hot water connec-
tions are on the top panel, middle front. 
This unit is designed to be installed vertically in the 
upflow position and can be installed on a closet plat-
If damage is found, a claim should be 
filed against the carrier immediately.
form (platform not provided), hung on a closet wall 
(use wall hanging kit option) or recessed in a wall 
between wall studs (use front panel kit option).
 
FEATURES
Non-corrosive drain pan, installed in sloped position, 
¾” female primary and secondary connections acces-
sible from either side or bottom.
Filters provided, are 1” throwaway accessible from 
the front.
Coils  and  fan  motor/blower  assemblies  accessible 
from the front, when installed with the optional front 
panel assembly. 
Front air return standard, optional bottom return avail-
able but requires bottom return option.
Options available are thermostats, wall front panels, 
condensate pan overflow switch, closet hanger bracket 
kit, bottom return air kit and chilled water coil valve 
packages.  Consult  applications  group 
@
  717-771-
7073 for details on ordering and availability of these 
options.
Cabinet is fully insulated with 1” coated fiberglass 
panels.
All units have 0” clearance to combustible surfaces, 
so the units can be installed against wall studs and 
drywall.
CLEARANCES
Clearance  required  in  front  of  the  unit  to  provide 
access to coils, electrical controls and motor/blower 
assembly. This clearance should be equal to the depth 
of the cabinet.
MOUNTING - YCW UNIT STYLE
Recessed In Wall
All units must be installed level to insure proper drain-
age and operation.
1.  Frame the unit as required so the front panel 
of the wall unit will be flush with the drywall 
surface when installed (see Fig. 3).