INSTALLATION
DUCTWORK
Ductwork recommendations are as follows:
• 
Insulate  to  prevent  condensation  during 
cooling.
• 
Size  to  the  unit  openings  are  generally 
acceptable but are determined by the engineering 
drawings.
• 
Be  sure  units  are  ducted  per  local  codes  or 
national codes, as applicable. 
WIRING
Units are provided with wiring diagrams and name-
plate data to provide information required for neces-
sary field wiring.  All wiring must comply with local 
and national code requirements.
Refer to Fig. 3 for access locations.
These units are provided with a class 2 transformer 
for 24-volt control circuits.  Should any add-on equip-
ment also have a class 2 transformer furnished, care 
must be taken to prevent interconnecting outputs of 
the two transformers by using a thermostat with isolat-
ing contacts. These units are supplied with a 3-speed 
control board.
The YCW  units  (2-pipe  cooling)  are  provided  as 
standard 120 volt power wired to a disconnect/terminal 
block and a ground lug. Fan motor hi, med and low 
speed leads are wired to the control board. There may 
be an unused motor lead from the motor – it needs to 
be capped off. The board is also wired to handle either 
24v or 120v control wiring. To use 24v, remove jump-
ers on the control board. To use a 24v chilled water 
control valve, wire the valve in series with the “Y” 
connection from the control box, max of 20va.
For 24v wiring using a T420 manual C/O, T421 auto 
C/O or the T200 speed control thermostats, you will 
need a 6-wire thermostat cable minimum.
The YCW-HW units (4-pipe heating/cooling) are 
provided as standard 120 volt power wired to a dis-
connect/terminal block and a ground lug. Fan motor 
hi, med and low speed leads are wired to the control 
board. There may be an unused motor lead from the 
motor – its needs to be capped off. The board is also 
wired to handle either 24v or 120v control wiring. To 
use 24v, remove jumpers on the control board. For 
your 24v hot water control valve, wire it in series 
with the “W” connection. For your 24v chilled water 
control valve, wire it in series with the “Y” connection. 
For 24v wiring using a T420 manual C/O, T421 auto 
C/O or the T200 speed control thermostats, you will 
need a 7-wire thermostat cable minimum.
The YCWE units (2-pipe cooling w/electric heat) 
are provided as standard 208/240 volt power wired 
to a disconnect switch with a ground lug. Fan motor 
hi, med and low speed leads are wired to the control 
board. There may be an unused motor lead from the 
motor – its needs to be capped off. The board is also 
wired to handle either 24v or 120v control wiring. 
To use 24v, remove jumpers on the control board. 
The transformer in the control box is 208/240v with 
a common terminal, one for 208v and one for 240v. 
Transformer is wired 240v from factory; for 208v ap-
plication, move the ORG wire on the transformer to 
the 208v terminal. For your 24v chilled water control 
valve, wire it in series with the “Y” connection. When 
using a T420 manual C/O, T421 auto C/O or the T200 
speed  control  thermostats,  you  will  need  a  7-wire 
thermostat cable minimum. See Table 2 for MCA and 
MFS for each unit size/electric heat KW size.
Any devices such as fan switches or 
thermostats that have been furnished 
by  the  factory  for  field  installation 
must be wired in strict accordance with 
the  wiring  diagram  that  is  supplied 
with the unit. Failure to do so could 
result in damage or injury.