York LD11554 User Manual

Page of 12
JOHNSON CONTROLS
8
FORM 115.20-NOM6 (1106)
Drain Piping
Condensate drain lines must be installed with adequate 
slope away from the unit to assure positive drainage.  
Since the drain pan is located on the suction side of 
the blower, a negative pressure exists at the drain pan 
and a minimum trap of 1-1/2" must be provided in the 
drain line to assure proper drainage.
Drain connections, primary and secondary, are 3/4" 
MPT (see Fig. 5 for details).
On units with plastic drain pans the 
drain connections must be made hand 
tight only.
INSTALLATION
FIG. 5 – CWE SERIES WALL / CLOSET FAN COILS  
Chilled Water with Electric Heat
CONDENSATE DRAIN CONNECTIONS
(With drain cover removed)
(Thermoplastic pan shown)
LD12278