PIPING
All piping connections are 5/8" OD copper tubing 
(see Fig.4).
The  supply  and  return  piping  must  be  adequately 
sized to meet the design water flow requirements as 
specified for the specific installation.  All chilled water 
piping must be insulated to prevent condensation.  It 
is also recommended that all piping be insulated to 
prevent freezing when piping is run in an uncondi-
tioned space.
Coil freeze protection is recommended 
for applications where the fan coil is 
located in ambient air locations (attics, 
crawl spaces, etc.) or within structures 
that may be unoccupied during freez-
ing conditions.  Consult the factory for 
additional information.
Piping Precautions
• 
Flush all piping prior to connection to remove 
all debris.
• 
Use wet cotton rags to cool valve bodies when 
soldering.
• 
Open  all  valves  (midway  for  hand  valves, 
manually open on motorized valves) prior to 
soldering.
• 
When soldering to bronze or brass, heat the piping 
while in the socket/cup and begin introducing the 
solder when the flux boils rapidly.  Avoid direct 
flame into the solder joint.
• 
Heat can only be applied to the cup of the valve 
body for a minimal time before damage occurs 
(even with the use of wet rags).
• 
Avoid rapid quenching of solder joints, as this 
will produce joints of inferior quality.
• 
Connect  all  piping  per  accepted  industry 
standards and observe all regulations governing 
installation  of  piping  systems.    When  all 
connections are complete, the system must be 
pressure tested.  Repair any solder joint leaks and 
gently tighten any leaking valve packing nuts 
and piping accessories as required.  Hydronic 
systems are not designed to hold pressurized air 
and should only be tested with water.
When  connecting  piping  or  valve 
kits to fan coil units, do not bend or 
reposition the coil header tubing for 
alignment purposes.  This could cause 
a tubing fracture resulting in a water 
leak when water pressure is applied 
to the system
FIG. 4 – CW-HW SERIES UPFLOW WALL / CLOSET FAN COILS  
4-Pipe Chilled Water-Hot Water (190 - 1085 CFM)
INSTALLATION