York YPAL 050 User Manual

Page of 168
46
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
Installation
6.  The furnace and its individual manual shut-off 
valve must be disconnected from the gas supply 
piping system during any pressure testing of that 
system at test pressures in excess of 0.5 PSIG.
Disconnect gas piping from unit when 
leak testing at pressures greater than 
0.5 PSIG.  Pressures greater than 0.5 
PSIG will cause gas valve damage 
resulting in a hazardous condition.  
If gas valve is subjected to pressure 
greater than 0.5 PSIG, it must be 
replaced.
7.  A 1/8 inch N.P.T plugged tapping, accessible for 
test gage connection, must be installed immedi-
ately upstream of the gas supply connection to the 
furnace.
COMBUSTION VENT
The combustion vent assembly is shipped in the return 
air section of the unit.  The combustion vent assembly 
must be mounted over the fl ue gas outlet fi xed panel 
located to the right of the gas heat access door.  Install 
as follows:
1.  Remove the combustion vent assembly from the 
return compartment.
2.  Remove the vertical row of six screws on either 
side of the fl ue gas outlet fi xed panel.
3.  Mount the combustion vent assembly over the fl ue 
gas outlets and attach to the gas outlet fi xed panel 
using the screws removed in step 2.
4.  See Figure 2-14 for the proper orientation of the 
combustion vent.  The internal baffl e(s) must direct 
the fl ue gases upward.
FIG. 2-14 – COMBUSTION VENT
LD11766